TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
13
Fan Status
MSV 28
1 = Off
2 = Low
3 = Med
4 = High
BI1 Status
BI 29
0 = Deactivated
1 = Activated
BI2 Status
BI 30
0 = Deactivated
1 = Activated
UI3 Status
BI 31
0 = Deactivated
1 = Activated
Local Motion
BI 32
0 = No Motion
1 = Motion
Effective Occupancy
MSV 33
1 = Occupied
2 = Unoccupied
3 = Temporary Occupied
4 = Stand-by
Window Alarm
BI 35
0 = Off
1 = On
BI 36
0 = Off
1 = On
Service Alarm
BI 37
0 = Off
1 = On
Occupied Heat Setpoint
AV 39
40.0°F/4.5°C to
90.0°F/32.0°C
Occupied Cool Setpoint
AV 40
54.0°F/12.0°C to
100.0°F/37.5°C
Stand-by Heat Setpoint
AV 41
40.0°F/4.5°C to
90.0°F/32.0°C
Stand-by Cool Setpoint
AV 42
54.0°F/12.0°C to
100.0°F/37.5°C
Unoccupied Heat Setpoint
AV 43
40.0°F/4.5°C to
90.0°F/32.0°C
Unoccupied Cool Setpoint
AV 44
54.0°F/12.0°C to
100.0°F/37.5°C
Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects
(Part 3 of 7)
Point Name
Thermostat Point
(Type/Address)
Range