TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
18
TEC2645-4 Thermostat Controller
Table 4: TEC2645-4 MS/TP Bus Objects (Part 1 of 4)
Point Name
Thermostat Point
(Type/Address)
Range
Room Temp
1, 2
AV 7
-40.0°F/-40.0°C to
122.0°F/50.0°C
Room Temp Override
3
BV 8
0 = Normal
1 = Override
Outdoor Temperature
3, 4
AV 9
-40.0°F/-40.0°C to
122.0°F/50.0°C
Supply Temperature
AI 12
-40.0°F/-40.0°C to
122.0°F/50.0°C
AUX Command
BV 14
0 = Off
1 = On
Sequence of Operation
MSV 15
0 = Cooling Only
1 = Heating Only
2 = Cooling and Reheat
3 = Heating and Reheat
System Mode
MSV 16
1 = Off
2 = Auto
3 = Cool
4 = Heat
Fan Mode
MSV 17
1 = On
2 = Auto
Occupancy Command
MSV 18
1 = Resume Schedule
2 = Occupied
3 = Unoccupied
4 = Temporary Occupied
Keypad Lockout
MSV 19
1 = Level 0
2 = Level 1
3 = Level 2
4 = Level 3
5 = Level 4
6 = Level 5
PI Heating Demand
5
AV 21
0 to 100%
PI Cooling Demand
AV 22
0 to 100%
AUX (BO5) Status
BI 25
0 = Off
1 = On
Fan Status
MSV 28
1 = Off
4 = High
BI1 Status
BI 29
0 = Deactivated
1 = Activated
BI2 Status
BI 30
0 = Deactivated
1 = Activated
UI3 Status
BI 31
0 = Deactivated
1 = Activated
Local Motion
BI 32
0 = Deactivated
1 = Activated
Effective Occupancy
MSV 33
1 = Occupied
2 = Unoccupied
3 = Temporary Occupied
4 = Stand-by
Window Alarm
BI 35
0 = Off
1 = On