TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
23
BI2 Status
BI 30
0 = Deactivated
1 = Activated
UI3 Status
BI 31
0 = Deactivated
1 = Activated
Local Motion
BI 32
0 = Deactivated
1 = Activated
Effective Occupancy
MSV 33
1 = Occupied
2 = Unoccupied
3 = Temporary Occupied
4 = Stand-by
Window Alarm
BI 35
0 = Off
1 = On
BI 36
0 = Off
1 = On
Service Alarm
BI 37
0 = Off
1 = On
Occupied Heat Setpoint
3, 7
AV 39
40.0°F/4.5°C to
90.0°F/32.0°C
Occupied Cool Setpoint
AV 40
54.0°F/12.0°C to
100.0°F/37.5°C
Stand-by Heat Setpoint
AV 41
40.0°F/4.5°C to
90.0°F/32.0°C
Stand-by Cool Setpoint
AV 42
54.0°F/12.0°C to
100.0°F/37.5°C
Unoccupied Heat Setpoint
AV 43
40.0°F/4.5°C to
90.0°F/32.0°C
Unoccupied Cool Setpoint
AV 44
54.0°F/12.0°C to
100.0°F/37.5°C
BI1 Configuration
MSV 46
1 = None
2 = Rem NSB
3 = Motion NO
4 = Motion NC
5 = Window
BI2 Configuration
MSV 47
1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
UI3 Configuration
MSV 48
1 = None
2 = COC/NH
3 = COC/NC
4 = COS
5 = SS
Menu Scroll
BV 49
0 = No Scroll
1 = Scroll Active
Temperature Scale
BV 51
0 = °C
1 = °F
Out 1 (BO1 and BO2)
Configuration
MSV 53
1 = False
2 = True
Table 5: TEC26x7-4 and TEC26x7-4+PIR Series MS/TP Bus Objects (Part 2 of 4)