TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
46
Unoccupied Cool Setpoint
AV 44
54.0°F/12.0°C to
100.0°F/37.5°C
BI 1 Configuration
MSV 46
1 = None
2 = Rem NSB
3 = Motion N.O.
4 = Motion N.C.
5 = Window
BI 2 Configuration
MSV 47
1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
Menu Scroll
BV 49
0 = No Scroll
1 = Scroll Enabled
Auto Mode Enable
BV 50
0 = Disabled
1 = Enabled
Temperature Scale
BV 51
0 = °C
1 = °F
Pipe Number
MSV 52
1 = 2-Pipe
2 = 4-Pipe
Password Value
AV 56
0 to 1000
Fan Mode Sequence
MSV 57
1 = Low- Medium - High
2 = Low - High
3 = Low - Medium - High - Auto
4 = Low - High - Auto
5 = On - Auto
Heating Setpoint Limit
AV 58
40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit
AV 59
54.0°F/12.0°C to
100.0°F/37.5°C
Setpoint Type
BV 60
0 = Permanent
1 = Temporary
Setpoint Function
BV 61
0 = Dual Setpoints
1= Attached Setpoints
Table 11: TEC26xx-0+PIR (Part 3 of 5)
Point Name
Thermostat Point
(Type/Address)
Range