TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
28
Fan Control
BV 62
0 = Off
1 = On
Anticycle
MV 63
1 = 0 Minutes
2 = 1 Minute
3 = 2 Minutes
4 = 3 Minutes
5 = 4 Minutes
6 = 5 Minutes
Fan Purge Delay
BV 64
0 = Off
1 = On
DI1 Configuration
MV 65
1 = None
2 = Rem NSB
3 = RemOVR
4 = Filter
5 = Service
6 = Fan Lock
DI2 Configuration
MV 66
1 = None
2 = Rem NSB
3 = RemOVR
4 = Filter
5 = Service
6 = Fan Lock
Proportional Band
MSV 67
1 = 2 (2°F/1.1°C)
2 = 3 (3°F/1.7°C)
3 = 4 (4°F/2.2°C)
4 = 5 (5°F/2.8°C)
5 = 6 (6°F/3.3°C)
6 = 7 (7°F/3.9°C)
7 = 8 (8°F/4.4°C)
Unoccupied Time
AV 68
0.5 Hours to
24.0 Hours
TEC2601-address
8
Device 76aaa
9
TEC2601-4 to TEC2601-127
1.
This MS/TP Bus object is readable and only writable if the corresponding override is set. (For
example,
Room Temp
has a corresponding override object of
Room Temp Override
. This
corresponding override object needs to be set to
1 = Override
to be able to write
Room Temp
to a
different value.)
2.
This MS/TP Bus object is readable and writable.
3.
This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
4.
This MS/TP Bus object is readable and only writable when out of service.
5.
This BI object type status is available even if the configuration is set to
None
.
6.
This MS/TP Bus object requires that
Frost Protection
be set to
1 = On
.
7.
If one setpoint of a pair of heating and cooling setpoints (for example,
Occupied Heat Setpoint
and
Occupied Cool Setpoint
) is overridden, the other setpoint of the pair may be automatically adjusted
by the thermostat controller to maintain the minimum deadband between the two setpoints.
8.
The address range actually displays from
0
to
254
. Only choose an address within the
4
to
127
range.
9.
The designation
aaa
is the address of the device (from
004
to
127
) on the MS/TP network.
Table 6: TEC2601-4 and TEC2601-4+PIR MS/TP Bus Objects (Part 3 of 3)
Point Name
Thermostat Point
(Type/Address)
Range