TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
30
BI 38
0 = Off
1 = On
Service Alarm
BI 39
0 = Off
1 = On
Fan Lock Alarm
BI 40
0 = Off
1 = On
Occupied Heat Setpoint
7
AV 42
40.0°F/4.5°C to
90.0°F/32.0°C
Occupied Cool Setpoint
AV 43
54.0°F/12.0°C to
100.0°F/37.5°C
Unoccupied Heat Setpoint
AV 44
40.0°F/4.5°C to
90.0°F/32.0°C
Unoccupied Cool Setpoint
AV 45
54.0°F/12.0°C to
100.0°F/37.5°C
Temperature Scale
BV 47
0 = °C
1 = °F
Heating Setpoint Limit
AV 48
40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit
AV 49
54.0°F/12.0°C to
100.0°F/37.5°C
Heating Lockout Temperature
AV 50
-15.0°F/-26.0°C to
120.0°F/49.0°C
Cooling Lockout Temperature
AV 51
-40.0°F/-40.0°C to
95.0°F/35.0°C
Deadband
AV 52
2.0F°/1.0C° to 4.0F°/2.0C°
MV 53
1 = 3 CPH
2 = 4 CPH
3 = 5 CPH
4 = 6 CPH
5 = 7 CPH
6 = 8 CPH
Cooling CPH
MV 54
1 = 3 CPH
2 = 4 CPH
Frost Protection
BV 55
0 = Off
1 = On
Aux Contact
BV 56
0 = Normally Open (N.O.)
1 = Normally Closed (N.C.)
Menu Scroll
BV 57
0 = No Scroll
1 = Scroll Active
Password Value
AV 59
0 to 1,000
Power Up Delay
AV 60
10 to 120 Seconds
Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 2 of 4)
Point Name
Thermostat Point
(Type/Address)
Range