TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
25
Floating Motor Timing
(TEC2627-4 Model)
MSV 76
1 = 0.5 Minutes
2 = 1.0 Minute
3 = 1.5 Minutes
4 = 2.0 Minutes
5 = 2.5 Minutes
6 = 3.0 Minutes
7 = 3.5 Minutes
8 = 4.0 Minutes
9 = 4.5 Minutes
10 = 5.0 Minutes
11 = 5.5 Minutes
12 = 6.0 Minutes
13 = 6.5 Minutes
14 = 7.0 Minutes
15 = 7.5 Minutes
16 = 8.0 Minutes
17 = 8.5 Minutes
18 = 9.0 Minutes
On/Off Control CPH (TEC2627-
4 Model)
MSV 77
1 = 3 CPH
2 = 4 CPH
3 = 5 CPH
4 = 6 CPH
5 = 7 CPH
6 = 8 CPH
Direct/Reverse Acting
(TEC2647-2 Model)
BV 78
0 = Direct Acting
1 = Reverse Acting
TEC26x7-aaa
8, 9
Device 72aaa
N/A
1.
This MS/TP Bus object is readable and only writable if the corresponding override object is set. (For
example,
Room Temp
has a corresponding override object of
Room Temp Override
. This
corresponding override object needs to be set to
1 = Override
to be able to write
Room Temp
to a
different value.)
2.
This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
3.
This MS/TP Bus object is readable and writable.
4.
This MS/TP Bus object is valid only if it is written via the network.
5.
This MS/TP Bus object is readable only.
6.
The BI object type status is available even if the configuration is set to
None
.
7.
If one setpoint of a pair of heating and cooling setpoints (for example,
Occupied Heat Setpoint
and
Occupied Cool Setpoint
) is overridden, the other setpoint of the pair may be automatically adjusted
by the thermostat controller to maintain the minimum deadband between the two setpoints.
8.
The designation
aaa
is the address of the device (from
004
to
127
) on the MS/TP network.
9.
Max_Master is writable.
Table 5: TEC26x7-4 and TEC26x7-4+PIR Series MS/TP Bus Objects (Part 4 of 4)
Point Name
Thermostat Point
(Type/Address)
Range