TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
40
Eff Reset Humidification
RH Spt
AV 96
0 to 100%
Humidification High Limit Spt
AV 97
50 to 90%
Low RH Setpoint
AV 98
10 to 90%
Low Temp Reset RH Setpoint
AV 99
-40.0°F/-40.0°C to
15.0°F/-9.5°C
High Temp Reset RH Setpoint
AV 100
20.0°F/-6.5°C to
55.0°F/13.0°C
Humidifier Output
AV 101
0 to 100%
TEC2613-address
8
Device 76aaa
9
TEC2613-4 to TEC2613-127
1.
This MS/TP Bus object is readable and only writable if the corresponding override is set. (For
example,
Room Temp
has a corresponding override object of
Room Temp Override
. This
corresponding override object needs to be set to
1 = Override
to be able to write
Room Temp
to a
different value.)
2.
This MS/TP Bus object is readable and writable.
3.
This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
4.
This MS/TP Bus object is readable and only writable when out of service.
5.
This BI object type status is available even if the configuration is set to
None
.
6.
This MS/TP Bus object requires that
Frost Protection
be set to
1 = On
.
7.
If one setpoint of a pair of heating and cooling setpoints (for example,
Occupied Heat Setpoint
and
Occupied Cool Setpoint
) is overridden, the other setpoint of the pair may be automatically adjusted
by the controller to maintain the minimum deadband between the two setpoints.
8.
The address range actually displays from
0
to
254
. Only choose an address within the
4
to
127
range.
9.
The designation
aaa
is the address of the device (from
004
to
127
) on the MS/TP network.
Table 9: TEC2613-4 and TEC2613-4+PIR MS/TP Bus Objects (Part 4 of 4)
Point Name
Controller Point
(Type/Address)