TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
31
Temporary Occupancy Time
MV 61
1 = 0 Hours
2 = 1 Hour
3 = 2 Hours
4 = 3 Hours
5 = 4 Hours
6 = 5 Hours
7 = 6 Hours
8 = 7 Hours
9 = 8 Hours
10 = 9 Hours
11 = 10 Hours
12 = 11 Hours
13 = 12 Hours
Fan Control
BV 62
0 = Off
1 = On
Anticycle
MV 63
1 = 0 Minutes
2 = 1 Minute
3 = 2 Minutes
4 = 3 Minutes
5 = 4 Minutes
6 = 5 Minutes
Fan Purge Delay
BV 64
0 = Off
1 = On
DI1 Configuration
MV 65
1 = None
2 = Rem NSB
3 = RemOVR
4 = Filter
5 = Service
6 = Fan Lock
DI2 Configuration
MV 66
1 = None
2 = Rem NSB
3 = RemOVR
4 = Filter
5 = Service
6 = Fan Lock
Proportional Band
MSV 67
1 = 2 (2°F/1.1°C)
2 = 3 (3°F/1.7°C)
3 = 4 (4°F/2.2°C)
4 = 5 (5°F/2.8°C)
5 = 6 (6°F/3.3°C)
6 = 7 (7°F/3.9°C)
7 = 8 (8°F/4.4°C)
Unoccupied Time
AV 68
0.5 Hours to
24.0 Hours
Heat Pump Stages
MV 75
1 = One Stage
2 = Two Stages
High Balance Point
AV 82
34.0°F/1.0°C to
90.0°F/32.0°C
Low Balance Point
AV 83
-40.0°F/-40.0°C to
30.0°F/-1.0°C
Comfort Mode
BV 84
0 = Comfort
1 = Economy
Reversing Valve Configuration
BV 85
0 = Normally Heat
1 = Normally Cool
Table 7: TEC2602-4 and TEC2602-4+PIR MS/TP Bus Objects (Part 3 of 4)
Point Name
Thermostat Point
(Type/Address)
Range