TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
19
BI 36
0 = Off
1 = On
Service Alarm
BI 37
0 = Off
1 = On
Occupied Heat Setpoint
3, 7
AV 39
40.0°F/4.5°C to
90.0°F/32.0°C
Occupied Cool Setpoint
AV 40
54.0°F/12.0°C to
100.0°F/37.5°C
Stand-by Heat Setpoint
AV 41
40.0°F/4.5°C to
90.0°F/32.0°C
Stand-by Cool Setpoint
AV 42
54.0°F/12.0°C to
100.0°F/37.5°C
Unoccupied Heat Setpoint
AV 43
40.0°F/4.5°C to
90.0°F/32.0°C
Unoccupied Cool Setpoint
AV 44
54.0°F/12.0°C to
100.0°F/37.5°C
BI1 Configuration
MSV 46
1 = None
2 = Rem NSB
3 = Motion NO
4 = Motion NC
5 = Window
BI2 Configuration
MSV 47
1 = None
2 = Door Dry
3 = Override
4 = Filter
5 = Service
UI3 Configuration
MSV 48
1 = None
2 = COC/NH
3 = COC/NC
4 = COS
5 = SS
Menu Scroll
BV 49
0 = No Scroll
1 = Scroll Active
BV 50
0 = Disabled
1 = Enabled
Temperature Scale
BV 51
0 = °C
1 = °F
AUX (BO5) Configuration
MSV 54
1 = Not Used
2 = NO with Occ
3 = NC with Occ
4 = NO with Occ and Fan
5 = NC with Occ and Fan
6 = Network Controlled
Password Value
AV 56
0 to 1,000
Heating Setpoint Limit
AV 58
40.0°F/4.5°C to
90.0°F/32.0°C
Cooling Setpoint Limit
AV 59
54.0°F/12.0°C to
100.0°F/37.5°C
Setpoint Type
BV 60
0 = Permanent
1 = Temporary
Setpoint Function
BV 61
0 = Dual Setpoints
1 = Attached Setpoints
Table 4: TEC2645-4 MS/TP Bus Objects (Part 2 of 4)
Point Name
Thermostat Point
(Type/Address)
Range