TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
17
Direct/Reverse Acting
(TEC2646-4, TEC2646H-4,
TEC2646H-4+PIR, TEC2656-4,
TEC2656H-4, TEC2656-4+PIR,
and TEC2656H-4+PIR Models)
BV 78
0 = Direct Acting
1 = Reverse Acting
TEC26x6-aaa
7, 8
Device 73aaa
N/A
1.
This MS/TP Bus object is readable and only writable if the corresponding override object is set. (For
example,
Room Temp
has a corresponding override object of
Room Temp Override
. This
corresponding override object needs to be set to
1 = Override
to be able to write
Room Temp
to a
different value.)
2.
This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
3.
This MS/TP Bus object is readable and writable.
4.
This MS/TP Bus object is valid only if it is written via the network.
5.
This MS/TP Bus object is readable only.
6.
The BI object type status is available even if the configuration is set to
None
.
7.
If one setpoint of a pair of heating and cooling setpoints (for example, Occupied Heat Setpoint and
Occupied Cool Setpoint) is overridden, the other setpoint of the pair may be automatically adjusted by
the thermostat to maintain the minimum deadband between the two setpoints.
8.
Max_Master is writable.
Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects
(Part 7 of 7)
Point Name
Thermostat Point
(Type/Address)
Range