Johnson Controls
5513350-JTG-1018
69
Electrical Data (Continued)
Power Supply Voltage Limits
Table 36:
Power Supply Voltage Limits
Power Supply
Minimum Voltage
Maximum Voltage
208-230V/3Ph/60Hz
207
253
460V/3Ph/60Hz
414
506
575V/3Ph/60Hz
518
632
Condenser Fan Motor
Table 37: Condenser Fan Motor
Each Motor
208-230V/3Ph/60Hz
460V/3Ph/60Hz
6.8
3.4
Unit Size
Quantity of Fans
208-230V/3Ph/60Hz
460V/3Ph/60Hz
25–30 Ton
2
13.6
6.8
40–50 Ton
4
27.2
13.6
Electric Heat
Table 38:
Electric Heat Amp Draw
Capacity
Type of Heat
Heater
Nominal kW
Each
Stage kW Steps
208-30V/3Ph/60Hz
460V/3Ph/60Hz
575V/3Ph/60Hz
AMPS
AMPS
AMPS
25–30 T
ons
Low Heat
50
16.7
3
115.3
-
-
Low Heat with SCR
3*
Low Heat
60
20.0
3
-
69.2
55.3
Low Heat with SCR
3*
High Heat
100
16.7
6
230.5
-
-
High Heat with SCR
6*
High Heat
120
20.0
6
-
138.3
110.7
High Heat with SCR
6*
40–50 T
ons
Low Heat
60
15.0
4
138.3
-
-
Low Heat with SCR
4*
Low Heat
80
20.0
4
-
92.2
73.8
Low Heat with SCR
4*
High Heat
120
15.0
8
276.6
-
-
High Heat with SCR
8*
High Heat
160
20.0
8
-
184.4
147.5
High Heat with SCR
8*
NOTES:
* Silicon Controlled Rectifier (SCR) is a modulating electric heat option.
SCR electric heat is installed on the first stage of the unit and provides modulation from 0–100%.