Johnson Controls
5513350-JTG-1018
58
Electric Heat Data
Table 17: Electric Heat Performance Data
Model
Voltage
Size (kW)
Heat Capacity
(MBH)
Minimum Airflow
(CFM)
Maximum Temp.
Rise (°F)*
Low Heat
25–30 Ton
208/230
50
170.6
3,000
52.4
460/575
60
204.7
6,000
31.4
40–50 Ton
208/230
60
204.7
4,000
47.2
460/575
80
273.0
6,000
41.9
High Heat
25–30 Ton
208/230
100
341.2
6,500
48.4
460/575
120
409.4
8,500
44.4
40–50 Ton
208/230
120
409.4
8,000
47.2
460/575
160
545.9
12,500
40.3
NOTES:
* Maximum temperature rise is based on unit operation at the minimum airflow (CFM).
Hot Water Coil Data
Table 18:
Hot Water Coil Performance Data - 25–30 Ton (1 Row, Low Heat Option)
GPM
Water Pressure
Drop
CFM
Capacity (MBH) at Entering Water
140.0°F
160.0°F
180.0°F
200.0°F
10
0.8
5,000
107.8
137.8
167.9
198.3
6,000
124.4
159.1
194.0
229.1
8,000
135.7
173.7
211.9
250.3
10,000
144.2
184.7
225.3
266.2
12,000
150.9
193.3
235.9
278.8
20
2.9
5,000
125.7
160.2
194.9
229.8
6,000
149.4
190.4
231.8
273.3
8,000
166.5
212.3
258.4
304.8
10,000
179.9
229.5
279.4
329.5
12,000
190.7
243.4
296.3
349.5
30
6.4
5,000
132.9
169.2
205.7
242.3
6,000
159.9
203.6
247.5
291.6
8,000
179.7
228.9
278.3
328.0
10,000
195.6
249.1
303.0
357.0
12,000
208.6
265.8
323.2
380.9
40
11.1
5,000
136.9
174.1
211.6
249.2
6,000
165.7
210.8
256.1
301.7
8,000
187.1
238.2
289.4
340.9
10,000
204.5
260.2
316.2
372.5
12,000
218.8
278.5
338.4
398.7
Capacity Performance (Continued)