Johnson Controls
5513350-JTG-1018
70
Electrical Data (Continued)
Supply Fan and Return/Exhaust Fan Motor Data
Table 39:
Supply Fan and Return/Exhaust Fan Motor Data - Premium Efficiency - ODP
Motor HP
Nominal Voltage
208-230/3/60
460/3/60
575/3/60
FLA
FLA
FLA
Supply Fan Motor
5
14
6.6
5.3
7.5
20.4
9.7
8
10
26
12.5
10
15
38
17.8
14.2
20
52
23.5
19.1
25
64
29
24.5
30
76
35
29
40
99
49
40
50
121
57
46
Return/Exhaust
Fan Motor
3
8.5
4.2
3.4
5
14
6.6
5.3
7.5
20.4
9.7
8.0
10
26
12.5
10.0
15
38
17.8
14.2
20
52
23.5
19.1
Table 40:
Supply Fan and Return/Exhaust Fan Motor Data - Premium Efficiency - TEFC
Motor HP
Nominal Voltage
208-230/3/60
460/3/60
575/3/60
FLA
FLA
FLA
Supply Fan Motor
5
13.9
6.7
5.3
7.5
20
9.5
7.6
10
25.4
12
9.6
15
38
18.1
14.6
20
52
24
19.2
25
64
31
24
30
78
38
29
40
102
48
39
50
122
56
45
Return/Exhaust
Fan Motor
3
9
4.2
3.3
5
13.9
6.7
5.3
7.5
20
9.5
7.6
10
25.4
12
9.6
15
38
18.1
14.6
20
52
24
19.2