Johnson Controls
5513350-JTG-1018
17
Unit Size
25 Ton
30 Ton
40 Ton
50 Ton
Energy Recovery Wheel (ERW) - High CFM
Cassette Dimensions (L x W x H in inches)
50 x 4.36 x 50
50 x 4.36 x 50
62.42 x 6.07 x 62.42 62.42 x 6.07 x 62.42
Wheel Segments
6
6
8
8
Motor (V, ph, Hz)
208-230/3/60,
460/3/60, 575/3/60
208-230/3/60,
460/3/60, 575/3/60
208-230/3/60,
460/3/60, 575/3/60
208-230/3/60,
460/3/60, 575/3/60
Horsepower (HP)
1/6
1/6
1/4
1/4
Filter Type
2-inch MERV 8 Pleated
RA Filters - Size (Number)
25 x 25 (2)
25 x 25 (2)
15 x 20 (6)
15 x 20 (6)
OA Filters - Size (Number)
25 x 25 (2)
25 x 25 (2)
15 x 20 (6)
15 x 20 (6)
Energy Recovery Wheel (ERW) - Low CFM
Cassette Dimensions (L x W x H in inches)
44 x 4.36 x 44
44 x 4.36 x 44
56.19 x 4.36 x 56.19 56.19 x 4.36 x 56.19
Wheel Segments
6
6
6
6
Motor (V/ph/Hz)
208-230/3/60,
460/3/60, 575/3/60
208-230/3/60,
460/3/60, 575/3/60
208-230/3/60,
460/3/60, 575/3/60
208-230/3/60,
460/3/60, 575/3/60
Horsepower (HP)
1/6
1/6
1/6
1/6
Filter Type
2-inch MERV 8 Pleated
RA Filters - Size (Number)
25 x 25 (2)
25 x 25 (2)
15 x 20 (6)
15 x 20 (6)
OA Filters - Size (Number)
25 x 25 (2)
25 x 25 (2)
15 x 20 (6)
15 x 20 (6)
Electric Heat (208V/230V)
Size Range - Low/High (kW)
50/100
50/100
60/120
60/120
Heating Steps - Low/High
3/6
3/6
4/8
4/8
Electric Heat (460V/575V)
Size Range - Low/High (kW)
60/120
60/120
80/160
80/160
Heating Steps - Low/High
3/6
3/6
4/8
4/8
Gas Furnace
Staged Furnace Sizes
(input/output/stages)
250 / 202.5 / 2
500 / 405 / 2
500 / 405 / 2
750 / 607.5 / 4
750 / 607.5 / 4
1,250 / 1012.5 / 6
Airflow Range (min to max CFM)
5,000–12,000
8,000–20,000
Gas Heat Steady State Efficiency (SSE)
81%
81%
Modulating Furnace Sizes
(input/output/turndown)
250 / 202.5 / 10:1
500 / 405 / 20:1
500 / 405 / 20:1
750 / 607.5 / 30:1
750 / 607.5 / 30:1
1,250 / 1012.5 / 50:1
Airflow Range (min to max CFM)
5,000–12,000
8,000–20,000
Hot Water Coil
Coil Tube Diameter (inches)
1/2
1/2
1/2
1/2
Material
Copper Tube/
Aluminum Fin
Copper Tube/
Aluminum Fin
Copper Tube/
Aluminum Fin
Copper Tube/
Aluminum Fin
Fins Per Inch - Low/High
13/10
13/10
13/10
13/10
Size (H x L in inches) / Rows Low
25 x 70 / 1
25 x 70 / 1
42.5 x 70 / 1
42.5 x 70 / 1
Size (H x L in inches) / Rows High
25 x 70 / 2
25 x 70 / 2
42.5 x 70 / 2
42.5 x 70 / 2
Physical Data (Continued)
Table 1: Physical Data (Continued)