Johnson Controls
5513350-JTG-1018
112
Guide Specifications (Continued)
•
The warranty shall not include parts associated with
routine maintenance, such as belts, air filters, etc.
Compressor Warranty [Optional]
Manufacturer shall warrant all compressors of its manu
-
facture against defects in workmanship and material for a
period of 12 [60] months from date of shipment.
•
The warranty shall include parts [and labor] only dur
-
ing this period.
•
The warranty shall not include parts associated with
routine maintenance.
Delivery and Handling
1. Unit shall be delivered to the job site fully assembled,
wired, and charged with refrigerant and oil by the
manufacturer.
2. All handling and storage procedures shall be per
manufacturer’s recommendations.
Submittals
Shop Drawings
Shop drawing submittals shall include, but not limited to,
the following: drawings indicating components, dimen
-
sions, weights, required clearances, location, type and size
of field connections, and power and control wiring connec
-
tions.
Product Data
Product data shall include dimensions, weights, capacities,
ratings, fan performance, motor electrical characteristics,
and gauges and finishes of materials.
Documentation
1.
Fan curves with specified operating point clearly plot
-
ted shall be provided.
2.
Product data of filter media, filter performance data,
filter assembly, and filter frames shall be provided.
3.
Electrical requirements for power supply wiring, in
-
cluding wiring diagrams for interlock and control wir
-
ing shall be supplied. Factory and field-installed wir
-
ing shall be clearly indicated.
Equipment
Product Specification
Summary
Completely factory assembled, unitized construction, single
packaged air conditioning unit including a factory-mounted
and wired unit controller and sensors; single point power
with terminal block [dual point power with terminal block] [a
non-fused electrical disconnect], for main unit power shall
be factory-installed 460V [208-230V][575V] power supply,
outside air handling section with return and supply open
-
ings, discharge air (DA) plenum, direct-expansion refriger
-
ant condensing section. 5kA [65kA] short-circuit current rat
-
ing (SCCR). [Overcurrent protection must be Class J fusing
to obtain this 65kA SCCR. The unit shall be provided with
65kA SCCR equipment and AIC rating.]
Phase Monitor
A phase monitor shall be provided on unit designed to pro-
tect 3 phase equipment from phase loss, reversal, imbal-
ance, and low voltage. The phase monitor fault condition
shall be indicated at the unit control panel, and the unit shall
be placed into an emergency stop condition.
Internal Lights [Optional]
A discrete field powered 115V circuit of centrally located
marine LED lights shall be provided with individual wiring
run from the single switch located in the low voltage power
supply panel common wall. At a minimum lights shall be pro
-
vided in the [pre-evaporator blank], [post-evaporator blank],
economizer, evaporator coil, and supply fan sections.
Factory Test
1. On factory-assembled units, the refrigerant cir-
cuit shall be pressure-tested, evacuated, and fully
charged with refrigerant and oil.
2. On factory-assembled units, the unit controller shall
be configured and run tested at the factory to mini
-
mize field setup time.
3.
If the unit is not configured and tested, then the man
-
ufacturer shall provide field
start-up and testing to en-
sure that the controller is functioning properly.
4. Record test reports [optional] shall include end of line
quality test report to be sent out to the customer.