Johnson Controls
5513350-JTG-1018
60
GPM
Water Pressure
Drop
CFM
Capacity (MBH) at Entering Water
140.0°F
160.0°F
180.0°F
200.0°F
40
3.8
8,000
235.8
300.4
365.4
430.7
12,000
279.2
355.8
432.8
510.3
16,000
310.5
395.9
481.7
567.9
20,000
335.2
427.4
520.1
613.3
60
8.5
8,000
248.6
316.3
384.5
452.9
12,000
297.5
378.6
460.3
542.2
16,000
333.5
424.6
516.2
608.2
20,000
362.3
461.3
560.8
660.8
Table 21:
Hot Water Coil Performance Data - 40–50 Ton (2 Rows, High Heat Option)
GPM
Water Pressure
Drop
CFM
Capacity (MBH) at Entering Water
140.0°F
160.0°F
180.0°F
200.0°F
10
0.1
8,000
173.7
228.1
283.7
340.3
12,000
189.8
249.8
311.3
373.8
16,000
199.2
262.4
327.4
393.4
20,000
205.5
271.0
338.2
406.5
20
0.3
8,000
257.7
334.1
408.1
482.5
12,000
300.4
389.0
478.5
566.2
16,000
328.2
425.5
525.1
621.4
20,000
348.3
452.0
558.8
661.4
40
1.0
8,000
312.0
397.9
484.3
571.0
12,000
381.9
487.6
5940
700.9
16,000
432.2
552.3
673.0
794.5
20,000
471.1
602.3
734.1
866.8
60
2.1
8,000
332.3
423.2
514.4
605.9
12,000
414.5
528.3
642.7
757.4
16,000
475.9
606.8
738.4
870.7
20,000
524.5
669.1
814.5
960.7
Steam Coil Data
Table 22:
Steam Coil Performance Data - 25–30 Ton (Low Heat Option)
CFM
Capacity (MBH) at Steam Pressure (PSI)
2
6
10
15
5,000
205.6
220.7
233.7
247.7
6,000
244.3
262.3
277.7
294.4
8,000
273.2
293.3
310.5
329.2
10,000
296.1
318.0
336.0
356.9
12,000
315.4
338.6
358.5
380.1
Capacity Performance (Continued)
Table 19:
Hot Water Coil Performance Data - 40–50 Ton (1 Row, Low Heat Option)
(Continued)