JIF-2002 WEIGHING INDICATOR&CONTROLLER
50
◎
Built-in Automatic Program Mode: Loss-in-Weight Batching
(F101=4)
SP1 – Supplying Bin
Gate
SP2 – Full Flow Gate
Free – Dribble Flow Gate
Start signal – Pin22
1. The Weighing Hopper is empty as is the Receiving Bin. The display shows
"0", and all Gates are closed.
2. Open the Supplying Bin Gate.
3. When the GROSS Weight reaches "
SP 1
", the
SP 1
Output (Pin 12) signal
will come
ON
. Closed the Supplying Bin Gate by using the SP 1 Output ON
signal.
4. The displayed weight will exceed the SP 1 value by the Free Fall value.
This weight is not necessarily accurate - but accuracy is not needed at this
moment since the purpose of this event is to fill up the Weighing Hopper.
The SP 1 value is always compared to GROSS weight.
5. Input a TARE signal (Pin 24) to ZERO the display.
6. Input the Start signal via the Control I/O interface connector (Pin 22). When
the Start signal is received, the SP 2 and Free Outputs "come ON".
Note : When the Final Weight is 0, the Pin 11 and 10 are kept OFF .
7. Open the Full-Flow Gate and the Dribble-Flow Gate for Full-Flow filling into
the Receiving Bin.
Summary of Contents for JIF-2002
Page 1: ...JIF 2002 WEIGHING INDICATOR CONTROLLER 1 CHAPTER 1 INTRODUCTION ...
Page 5: ...JIF 2002 WEIGHING INDICATOR CONTROLLER 5 CHAPTER 2 INSTALLATION ...
Page 9: ...JIF 2002 WEIGHING INDICATOR CONTROLLER 9 CHAPTER 3 SPECIFICATIONS ...
Page 17: ...JIF 2002 WEIGHING INDICATOR CONTROLLER 17 CHAPTER 4 SYSTEMFUNCTIONS ...
Page 41: ...JIF 2002 WEIGHING INDICATOR CONTROLLER 41 CHAPTER 5 SET POINTS ...
Page 54: ...JIF 2002 WEIGHING INDICATOR CONTROLLER 54 CHAPTER 6 OPTIONS ...