JIF-2002 WEIGHING INDICATOR&CONTROLLER
53
6. When the display reaches "
Final - FREE
", the FREE Output (Pin 10)
signal will come
ON
. Closed the Dribble-Flow Gate by using the FREE
Output ON signal.
7. An Automatic Free Fall Compensation Command (Min. 200ms pulse to
Pin 21) may be given at this time
8. After Free Fall has stopped - check to see if the HI and LO (Pin 9, 8)
signals are OFF. If both outputs are OFF then the batch is completed
correctly.
9. Please input a TARE signal (Pin 24) and set point code, then preparing
another substance batching.
10. Load the next substance into the Supplying Bin. Prepare the proper
Program, Operator Settings (if needed). Repeat Steps 3 ~ 8.
11. Use the FREE (Pin 10) signal to delay a time period as the control signal
is processing to empty the Weighing Hopper.
12. When the GROSS weight is below the ZERO band, the ZERO Band
Output will come ON which signifying the Weighing Hopper is empty.
Closed the Weighing Hopper Discharge Gate by using the ZERO Band
(Pin 13) Output ON signal.
13. You are now ready for your next batching event.