jablotron JA-101K Manual Download Page 25

JABLOTRON

ALARMS

a.s.

Pod

Skalkou

4567/33

46601

Jablonec

n.

Nisou

Czech

Republic

www

.jablotron.com

||

|

JA-101K(-LAN)(-LAN3G) and JA-106K(-3G) 
Security System Control Panels 

25

 / 

110

 

MLJ51410

 

5.12  Use of existing cabling in refurbishment projects. 

  For the installation of new lines you should preferentially use the CC-01, CC-02 and CC-03 cables. 

  In  case  of  connection  to  cables  of the  SYKFY 3x2x0.5  type  the  data  wires  of  the  BUS  (A, B) must  be 

connected  to  one  selected  twisted  pair.  For  the  +12 V  power  supply  and  GND  you  can  connect  the 
respective wires together in the remaining two pairs (doubling within a pair). 

  In case of connection to cables of the UTP the data wires of the BUS (A, B) must be connected to one 

selected twisted pair. For the +12 V power supply and GND it is suitable to connect together (double) the 
respective wires of the remaining wire pairs. 

If a shielded cable is used, do not connect the shield to the BUS terminals! We recommend to bond all 

the  shields  (tinning)  in  the  control  panel  to  an  auxiliary  terminal  and  not  to  connect  this  bonding 
anywhere else. Also leave the other end of shielding at the device side unconnected. 

6  Use of wireless devices 

In the JA-100 system you can use wireless device of the JA-15x, JA-16x and JA-18x series. The control panel 

must be equipped with at least one JA-11xR radio module.  

When installing individual device observe the instructions in their manuals. 

6.1 

Installation of a JA-11xR radio module 

1.  The  module  can  be  placed  in  the  control  panel  cover  or  it  can  be  installed  elsewhere  in  the  building  and 

connect it with a BUS cable. If the module is installed in the control panel cover, connect it to the internal 
BUS connector using a flat cable equipped with RJ connectors. 

2.  If  the  control  panel  is  installed  in  a  place  with  poor  GSM  signal  reception,  the  GSM  module  increases  

its  transmission  power,  which  can  have  a  negative  impact  on  the  radio  module  communication  range.  
In such a case you are recommended to place the radio module outside the control panel, namely at least  
2 m from it, where it will not be negatively influenced anymore and will have higher-quality radio reception 
from the devices, which will allow for longer ranges and consequently installation distances. 

The RJ BUS connector on the control panel board is exclusively 

designed for the connection of a radio module installed inside the 
control panel housing. 

3.  You can cover a larger area with radio signal by installing up to 3 radio modules in different places (e.g. each 

one on a different floor). Signals from a wireless device (hereinafter device) can be received by more radio 
modules simultaneously. The control panel communicates in a cycle with individual radio modules, so it will 
get  information  sent  by  a  device  from  the  radio  module  that  was  the  first  to  receive  an  intact  signal  and 
reacts to it. Then, it will not get the same information from the other radio modules any more even though  
it was received with a stronger signal. Thus, it may happen that signals from the same unidirectional device 
may  exhibit  quite  different  data  in  F-Link / System  settings / Diagnostics  during  repeated  measurements 
depending on from which module the signal was taken. As regards to bidirectional devices, the control panel 
“reserves” the once used channel (communication with the first radio module) and after that it communicates 
with  the  particular  device  via  this  radio  module  only  (shown  in  Diagnostics,  the  Channel  column)  until  
the device stops responding. Then, it looks for the connection signal in the other radio modules. If you need 
to verify the quality of connection of individual devices to individual radio modules, check it by the RF signal 
graph  in  the  F-Link  SW  (button  on  the  upper  toolbar).  There  select  the  radio  module  for  which 
communication  should  be  checked  and  the  activate  devices  you  want  to  check.  A  graph  of  radio 
communication  shows  the  RF  signal  strength  measured  by  a  specific  radio  module.  It  is  also  possible  
to have several RF signal windows open so you can very simply monitor the RF coverage in that premises. 

4.  Install a radio module vertically on a wall. It must not be  situated near objects that  shield or interfere with 

communications (metals, electronic devices, cables, pipelines etc.). 

5.  After switching the system on you must 

enroll the radio modules first.

 It is only then that you can enroll 

wireless, see following chapter. 

6.2 

Installation of wireless devices – enrollment mode 

Wireless  devices  have  to  be  enrolled  to  the  system  for  instance  by  a  production  code.  The  enrollment 

procedure  can  be  performed  in  Enrollment  mode  only  using  a  PC  with  installed  F-Link  software. 
See chapter 8.4.1 Enrolling and erasing devices. 

 

Summary of Contents for JA-101K

Page 1: ...ce 10 2 System size 12 2 1 External size 12 2 2 Internal size system range 12 2 2 1 Configuration and splitting 13 3 Types of control panels utility parameters 14 3 1 Description of JA 101K LAN LAN3G...

Page 2: ...ustic indication 54 9 15 Time limited access for users 54 9 16 Disabling and blocking options 55 9 16 1 Disabling 55 9 16 2 Blocking 55 9 17 Non alarm functions Functions of PG outputs 56 10 Setting t...

Page 3: ...the control panel 100 13 Firmware updates 101 13 1 General firmware update rules FW 101 13 2 FW updates for the control panel and devices connected to the BUS 101 13 3 FW updates for wireless devices...

Page 4: ...de by activating a panic button or using a wireless remote control Duress access control serves for triggering of a silent alarm by authorization only or by system control setting unsetting PG control...

Page 5: ...egments by activation of detectors remote controllers by an event in the system e g setting a section alarm triggering by a calendar action using an SMS command by ringing of an authorized user or thr...

Page 6: ...least three segments are used Partial set is adjustable for each section separately If partial set is on the system does not react to intrusion detectors with the parameter internal set i e monitor th...

Page 7: ...ective ARC on registration of the control panel to MyJABLOTRON If this function is activated then after replacement of the used SIM card with another one the system will automatically delete the ARC s...

Page 8: ...t performed during the entrance delay then an alarm from the delay zone will be triggered Delay A Variant 2 Entrance to the protected premises system is SET through the rear door or garage door trigge...

Page 9: ...If prefix is selected The administrator code has to always begin with a 1 prefix if prefix is selected The default codes are filled in automatically by the F Link software so from the first activatio...

Page 10: ...no of users in the system 1 3 10 8 no of users in the system 1 3 Using an RFID card with 14 characters only 6 fixed 8 variable 108 100 000 000 10 8 100 000 000 10 8 100 000 000 Code with prefix and C...

Page 11: ...uring the voltage physical state Service technician Once per year Detectors Clean up the dust and dirt Administrator Once per year Test of functions test of RF range for wireless detectors For detecto...

Page 12: ...tion method is determined by the module selection RFID card tag reader keypad RFID reader keypad with an LCD display RFID reader The module also enables opening of a door lock by application of a card...

Page 13: ...t control level of the very basic sections Not for 2nd and 3rd levels of common sections When all sections assigned to the 2nd or 3rd level of common section are set then every common section is set a...

Page 14: ...er of radio modules 3 3 SMS reports up to 8 users up to 25 users Voice reports up to 8 users up to 15 users Recommended 12 V backup battery 2 6 Ah 18 Ah Maximum continuous current consumption availabl...

Page 15: ...unicator which can be connected to the Internet and with the ability to send data to secure mass storage areas the so called cloud images taken by PIR detectors with a camera or photo verification cam...

Page 16: ...panel 1pc Fuse T 0 2 A 250 V meant to protect a 230 V circuit 1pc Fuse T 0 4 A 250 V meant to protect a 110 V circuit 4pcs warning stickers 3pcs Fasteners 8 mm 3pcs Screws 40 mm 2pcs Ties 100 mm Dril...

Page 17: ...former 3 Back up battery 4 Attachment strap of the back up battery 5 cabling space 6 GSM antenna 7 Panel lid tamper pins Including spare tamper pins 8 Control panel PCB Parts of the JA 101K control pa...

Page 18: ...is a one special connector on the JA 101K LAN designed for a tamper contact to be connected It indicates any attempt at damaging the front cover or opening the control panel A rear tamper contact is n...

Page 19: ...ts follow their manuals the general design principles of fire alarm systems and instructions provided by the manufacturer during the certification training If you have any unclear points phone the Jab...

Page 20: ...is only for the JABLOTRON 100 system and it cannot be shared with another system not even to power different devices For powering other systems by BUS smart home automation use the JA 121T interface...

Page 21: ...ure Star BUS structure Daisy chain Star tree BUS structure The BUS cable must not be connected in such a way to create a closed loop of any wire the ends of individual branches must never be interconn...

Page 22: ...e than the minimum allowed voltage of 10 V must be available for all the devices For proper functioning of the connected devices the maximum allowed voltage loss is 2 0 V Unexpected voltage loss can b...

Page 23: ...segments 1 18 mA JA 110M module for magnetic sensors 5 mA 2 10 mA JA 110P PIR motion detector 5 mA 5 25 mA JA 110ST fire detector 5 mA 2 10 mA JA 110A internal siren 5 mA 1 5 mA JA 111A external back...

Page 24: ...for 12 hrs Imax 0 17 A 0 05 A 0 12 A subtract the control panel self current 0 05 A The current taken from each BUS output terminal is shown in the F Link SW in the Diagnostics tab on line 0 where th...

Page 25: ...J BUS connector on the control panel board is exclusively designed for the connection of a radio module installed inside the control panel housing 3 You can cover a larger area with radio signal by in...

Page 26: ...can find magnetic detectors glass break detectors shake tilt detectors and also infrared barriers The only specific thing is that main doors or garage doors are usually delayed and the rest of the zo...

Page 27: ...ntrol panel Disable device trouble autobypass NO YES Control panel Delayed report to ARC NO NO Control panel Ways of setting Set with warning NO Control panel Authorization type Standard NO Control pa...

Page 28: ...nel Daily reset of device autobypass NO YES Control panel Blocking when setting YES YES Control panel Unsetting cancels alarm YES YES Control panel Unsuccessful setting YES YES Control panel Disable d...

Page 29: ...e 2 Passable Impassable Passable Impassable Passable Impassable Active tamper 5 5 5 Active input any input 5 Active instant input 5 5 5 Active alarm memory indication 5 5 RF device 20 min no response...

Page 30: ...e premises opening windows and doors is allowed Smoke temperature detectors gas leak detectors flood detectors or panic buttons can trigger an alarm all the time Also tamper contacts of all devices al...

Page 31: ...same or lower level of authorization to control sections and PG outputs assign them with access codes RFID tags and cards Has permission to erase the alarm memory in assigned sections When Administrat...

Page 32: ...the control panel using a USB cable the administrator may get authorized remotely using the voice menu Service and ARC controls the system This is for the service and ARC technicians to control Set un...

Page 33: ...d confirmation by a code if the user has assigned both to double authorization which means obligatory applying of the card and code User code confirmation by a card to reduce the risk of unauthorized...

Page 34: ...py the respective number of consecutive position by one enrollment e g the JA 110M module which has two alarm inputs will occupy two positions Caution inadvertent deletion of device enrolled on other...

Page 35: ...ections that belong to it will be set at the same time This reaction also has the Unset function Mute Silencing of the internal siren with a subsequent report of the presence of a person in the buildi...

Page 36: ...d for the respective alarm input and the corresponding sensor is excluded from further activity If these three activations occur during an alarm three alarm SMS messages are generated altogether and t...

Page 37: ...he cause of event it is recorded to the events with a time stamp On all system keypads all alarms except silent panic alarm are indicated by red flashing of the backlit indication button with a contin...

Page 38: ...ntrol is performed see chapter 9 10 where the standard user code is modified 2 Audible panic is a usual alarm event with a beginning and an end so it is indicated acoustically by siren and keypad It c...

Page 39: ...on column and communication with the control panel is lost no response within a pre set time then the system triggers the event Fault activation and according to the Loss of a BUS device it can be fol...

Page 40: ...hone number and control system by DTMF tones after authorization SMS message Cell phone GSM dialler Authorized command for setting or unsetting sections and also control of PG outputs Dialling in from...

Page 41: ...ic function of the system keypad The system can be set fully or partially The system can be controlled from the LCD keypad menu or by control segments Using segments you can perform setting according...

Page 42: ...segment with authorization to cancel this indication or using the LCD keypad menu and selecting the option Cancel warning indication 2 Variant 2 of system control Default profile Setting the system T...

Page 43: ...ow 1x every 2 sec Fault indication on keypad in sleep mode valid for EN50131 1 profile only Button flashes red 1x every 2 sec Alarm memory indication on keypad in sleep mode valid for EN50131 1 profil...

Page 44: ...tected premises to inform them about the fact that the system has been set by an automatic timer During this time the user has to go to the system keypad immediately and unset the section in the usual...

Page 45: ...pre set Function blocking action by the calendar Every planned action can be blocked by one optional PG output Blocking means when a PG output is activated then a specific action won t be performed fo...

Page 46: ...press 0 and then Press star 1 To record section names press 1 then enter the number of section that you want to record and then Press star 2 3 4 5 To record messages of report A B C D press 2 3 4 5 a...

Page 47: ...whole system The texts of the command used to control PG outputs are editable the other texts cannot be changed There are no factory commands to control PG outputs it is necessary to set them first Co...

Page 48: ...ction 7 Name and status of Section 8 GSM signal quality Time and date of handing over the SMS to the GSM network COM info about communication Authorization Service JABLOTRON 100 GSM 90 DATA ok CELLID...

Page 49: ...Section 7 Set with an active zone GSM 90 Time 17 01 22 7 Installation name in accordance with the Initial setup tab Status Name and status of Section 1 Name and status of Section 3 Name and status of...

Page 50: ...le sections For more info see chapter 15 MyJABLOTRON web application Part of remote programming from the website regardless of the platform of the remote computer is so called WEB Link which is availa...

Page 51: ...e system from setting when they occur impassable obstacles One of the most common obstacles is any system fault indicated by a yellow keypad backlight indication button a loss of connection with a wir...

Page 52: ...g to set with a fault or a triggered device the keypad flashes for 8 sec after which the system will automatically set It s possible to set the system by pressing the segment button again or by pressi...

Page 53: ...l 2 17 Flooding SMS alerts 1 Alarm call 2 18 Code breaking attempt SMS alerts 1 Alarm call 2 19 Set with active zone when confirmation enabled SMS alerts 1 Alarm call 2 20 Section without movement SMS...

Page 54: ...Setting with an active zone until FW 13 only Permanent rapid beeping PG status indication quick beeping Permanent slow beeping Exit delay PG status indication slow beeping Continuous squeaking Entranc...

Page 55: ...tector input it blocks its activation The system ignores any detector activation an alarm is not triggered nor reports PG activation Tamper alarms faults or low battery reports are supervised all the...

Page 56: ...vices will be inactive Useful for indication of some single or collective statuses typically of open windows garage doors etc on the keypad control segment In similar ways statuses of all sections ala...

Page 57: ...f devices or records of the last battery replacement etc The F Link software can also be used to change the language of the control panel for communication with users The language does not only refer...

Page 58: ...er with the activation code will be sent shortly after that The activation code may contain 8 to 14 numerals and case sensitive letters Example of sending a request using an SMS The received activatio...

Page 59: ...f settings from the LCD keyboard will be disabled menu item Settings will be disabled After disconnection of the cable the item will re appear in the menu in a few seconds 4 After proper authorization...

Page 60: ...ith the sequential number of the code prefix If this parameter is disabled only a 4 digit access code is required to be entered and the codes may only be changed by the system Administrator who will a...

Page 61: ...on in a particular section The system distinguishes two types of alarms EW external warning and IW internal warning In the settings of the sirens you can determine which type of warning they should re...

Page 62: ...description of all the reactions in chapter 8 4 2 List of applicable reactions Internal this parameter is only available for intrusion detectors Signals from devices with this indication are not eval...

Page 63: ...keypad on the selected position in the system see chapter 5 Installation of BUS devices On entering in the internal settings of the keypad the Devices tab the following window will open the example re...

Page 64: ...not be unset Fire The segment triggers the fire alarm Then fire alarm is released from the section the segment is assigned to Audible Panic The segment makes it possible to release a loud alarm After...

Page 65: ...plementary the PG output to control The function is e g used to control a garage gate with a PG output impulse while the control segment displays the actual status of the gate obtained from the gate d...

Page 66: ...of a key segment or front cover Indicates PG status changes Optical indication of a PG s output status changes on a segment It is related to the indication settings options 2 4 If disabled the PG out...

Page 67: ...ections control from menu in a keyboard that contains an LCD screen you can define which sections can be enabled and disabled from the menu This way you can e g create a keypad that normally controls...

Page 68: ...Intermittent 50 50 Continuous Maximum siren time limitation of the maximum hooting time to 1 to 5 minutes supposing the control panel alarm is longer otherwise it stops together with the control pane...

Page 69: ...ected to a USB port of the computer by application of the RFID card tag using any keypad with a current FW version and applying an RFID card tag Authorization defines user rights The authorizations on...

Page 70: ...and when the activation condition is valid longer than set in the Time column suitable e g for indication of forgotten closing of a garage gate Extended copy copies activation of a device or internal...

Page 71: ...ght of the segment Test possibility to control an output manually from the computer Depending on the selected function it will enable or disable the particular PG if it s not currently blocked Note ma...

Page 72: ...the _ character is a blank space The code before the command is not obligatory if in the Communication tab the Voice menu and control SMS without a code item is enabled and the phone number of a user...

Page 73: ...hed table The basic structure of the voice menu is described in the attached table 9 5 To make changes in this tab you do not need to be in the Service mode Items marked this way are displayed if Adva...

Page 74: ...ted typically reports of failures and restoration of power supply or possibly setting with an active device only for selected users administrator etc User defined 2 special 2nd group where the install...

Page 75: ...roups Check reports this button bottom bar is used to set Check Ringing or Check SMS Report sent to a defined user every day at a defined time Special reports The button on the open programming table...

Page 76: ...can only be selected for manual time adjustment The change occurs on the last Sunday of March or October respectively at 1 00 UTC i e e g 2 00 CET or 3 00 CEST Time adjustment Internal time and date...

Page 77: ...message on LCD disappears automatically when the service technician locally accesses the system The annual check counter performs a reset Duress access control Serves for triggering of a silent alarm...

Page 78: ...tion from pre set system profiles according to requirements Default Parameters set by factory default with the option to modify them according to needs EN50131 1 Grade 2 Some parameters are pre set au...

Page 79: ...Unblocking or by authorized access from the ARC meant for Great Britain Unblocking after tamper alarm triggering can be performed also by a user with a service authorization meant for the Benelux are...

Page 80: ...the reaction Confirmed immediate Confirmed delayed A 1 60 min Waits for confirmation of fire by another detector Waiting time for fire alarm confirmation by another detector Valid for all detectors wi...

Page 81: ...every Monday Time Defines at what time the action is executed on the specified day Guarding Allows you to execute the actions Set Partially set with the variant Immediately no exit delay or acoustic...

Page 82: ...ed out on this day However the program valid for Sundays will be kept This way you can adjust the control of Sections or PG Control e g also for company holidays etc The Off attributed means disabled...

Page 83: ...several methods of remote communication configuration Without remote configuration it behaves like an autonomous device with its own SIM card The device communicates outwards sends SMS and voice mess...

Page 84: ...he communicator it only reduces connection of the module to 1 network cell unstable communication You can also get information about the signal quality using the SMS command STATUS see 9 6 SMS command...

Page 85: ...id SIM card if supported by the operator You can obtain the command from your operator Credit position in text position sequential number of the character in the operator s credit balance report at wh...

Page 86: ...limits the range of actual calling from 5 to 250 minutes a day Remote control via telephone setting the possibility to control the system remotely using the voice menu If Users are selected the menu...

Page 87: ...ted which considerably simplifies setting of the communication part of the system To make changes in this tab you do not need to be in the Service mode ARC enabled possibility to disable the set commu...

Page 88: ...rm Engineer reset Uncategorised 1314 YG ARC setting erased Uncategorised 1344 XQ RF jamming RF interference Faults and service events 1350 YC Event to ARC not delivered Uncategorised 1354 YS Event to...

Page 89: ...3151 GR Gas leak deactivation Fire 3154 WR Flood alarm deactivation Tamper 3170 UR Special Reaction A deactivation Special reports 3171 UR Special Reaction B deactivation Special reports 3172 UR Speci...

Page 90: ...controls 3690 RO PG30 OFF PG controls 3691 RO PG31 OFF PG controls 3692 RO PG32 OFF PG controls Source code Description 001 120 Devices 501 800 User codes 500 Service code 901 Control panel 921 ARC1 9...

Page 91: ...e backup battery is displayed If the voltage data of a wireless device are missing the device has not communicated yet activating its transmission e g by means of the tamper sensor or in F Link click...

Page 92: ...op bar after the name The toolbar provides immediate access to virtual keyboards system events settings RF signal of radio modules site map mode changes local and remote access to the control panel 11...

Page 93: ...n several formats FDE PDF TXT CSV XML HTM or HTML The FDE suffix makes it possible for the F Link to download the events again Events online available also after pressing F7 in a temporary table all e...

Page 94: ...ttings are recorded in the history arranged by the date and time and also all setting changes 5 You can import settings from another installation to the system e g after replacing an old control panel...

Page 95: ...have selected a function that can only be changed in the Service code On the start of the SW the Service Code was not entered and you do not have the authorization This is a setting that cannot be cha...

Page 96: ...the DIP switches for proper binary setting of the address and function of the module 11 4 RF Signal Window for graphic representation of radio band interference intensity with the possibility to selec...

Page 97: ...of setting can be done in all tabs except the Settings tab and the Service mode changes can be done in the Devices tab incl enrolling changes of internal settings and deletion of devices 11 7 Refresh...

Page 98: ...Information about the way of establishing the GPRS LAN connection and the sent and received amount of data is displayed in the bottom right corner 11 10 Installation Wizard An assistant for gradual p...

Page 99: ...saved by the software after the print so they are not available for possible repeated print 11 14 History of Settings The control panel saves the settings of all devices with changes of their program...

Page 100: ...t obligatory 2 Open the control panel cover Reset requires that the tamper contact must be active If the condition of point 1 was not fulfilled an alarm will be released 3 Disconnect the USB cable fro...

Page 101: ...the time of the F Link download It s up to date status is automatically guaranteed at the time when F Link is downloaded Location of the Automatic Update parameter 13 2 FW updates for the control pan...

Page 102: ...pletion of the update disconnect the USB cable reinsert batteries or connect the power supply and make the module complete 11 Perform a check in accordance with the description in the chapter Check af...

Page 103: ...does not contain any sensitive data as phone numbers of users or their access codes or other confidential data The saved file achieves the size on the order of hundreds of KB and therefore it can be d...

Page 104: ...AC supply failure without battery charging otherwise 550 mA depending on battery charge JA 111H Detector connection module 5 consumption of the connected external sensor 5 consumption of the connecte...

Page 105: ...on camera 15 250 With high intensity of IR ilumination JA 120PW Dual PIR detector with microwaves 5 25 JA 122E BUS external RFID reader 15 15 JA 123E BUS external keypad with an RFID reader 15 15 JA 1...

Page 106: ...wed take photos from verification devices monitor the course of temperature in the building or outdoors incl notification of exceeding of the lower or upper limit of set temperatures at a defined time...

Page 107: ...ust be allowed by the building owner in his her settings In the Installation Management application you will also find a complete log of the technical events of the alarm with a graphic representation...

Page 108: ...S tags etc 4 Partial setting at home Difference in indication between partial and full setting 5 Control of home automation using control segments and other functions Panic Fire health troubles 6 Trig...

Page 109: ...ion latest events incl date and time Power supply unit type A EN 50131 6 GSM communicator 850 900 1800 1900 MHz 3G GSM communicator 850 900 1800 1900 2100 MHz Environmental class class II indoor gener...

Page 110: ...JA 101K LAN LAN3G and JA 106K 3G Security System Control Panels 110 110 MLJ51410 NOTES...

Reviews: