EN
31
2.1.2.1. ALARM SETTING
While setting the alarm, if any detector is triggered (e.g. an open window) the system will react in
one of the following ways (based on the system confi guration):
:: Detectors will guard automatically after they switch to a standby mode (default setting).
:: The system will optically indicate triggered detectors with a segment fl ashing red for
8 seconds and the system will set automatically once this period has expired.
:: Setting the section with triggered detectors is also possible by pressing the segment button
on the right side repeatedly. This way a user confi rms an intention to set the section with
a triggered detector (e.g. an opened window). Otherwise the section with the triggered detector
will not be set.
:: A triggered detector will prevent the section from being set. This status is optically indicated by
a fl ashing red segment button. The detector preventing setting will be shown in the menu
on the keypad’s LCD display.
An unsuccessful setting is indicated by the indication button fl ashing yellow (“Unsuccessful setting”
parameter must be enabled).
Consult the installation with a service technician in order to program
the desired behavior of the system.
2.1.2.2. ALARM UNSETTING
Note
: If the “Unset section by authorization only during entrance delay” parameter is enabled, then
mere authorization will unset such section where the entrance delay has been triggered.
2. Press the right button
(the one which isn’t lit up) to set
a particular section. It is possible
to set more sections subsequently.
The delay between sections
selection must not be longer than
2 seconds.
3. The command
is executed
and the keypad acoustically
indicates the exit delay. The section
is set now, only the detectors with
a “Delayed Zone” reaction provide
time to leave the guarded area
during the exit delay. The segment
button of the set section turns red.
1. Authorize using
the keypad.
Sections which can be controlled
are lit up and the backlit indication
button will start fl ashing green.
1. When you enter the building
(triggering a detector with
a “Delayed zone” reaction), the
system starts indicating entrance
delay with a continuous tone and
segment button of the section in
which the delayed entrance has
been triggered fl ashing green.
Authorize yourself using
the keypad
– the green indication light of the
authorization panel starts fl ashing.
2. Press the left segment
button
of the section you want to unset.
3. The command is executed
and the segment buttons turn green
to indicate unset sections
Summary of Contents for 100+
Page 2: ...JABLOTRON 100...
Page 25: ...SCAN ME...