altered: 18.05.2017
additional manual
J3 C
+
J3C S
actuators
with Positioner (DPS)
technical changes reserved
Dat.: 10 08 14 0
compiled:
03.02.2017
Name:
AB
Functions of status LEDs
External status indicator LED
status
time
indicator
LED colour
reached position
100% 1111 1111 1111 1111
blue
power supply on / actuator moving to
„open “
100% 1111 1111 1111 1111
blue / green (flashing)
power supply on / actuator moving to
“closed “
100% 1111 1111 1111 1111
blue / red (flashing)
For further information about status functions consult our
“Basic instruction
J3 S
+
J3C S
“.
Status-LED DPS board (internal) (Abb. 4)
- OPEN
control signal
“OPEN” – actuator moving to “OPEN”
- CLOSE
control signal “CLOSE” – actuator moving to “CLOSE”
- OPEN+CLOSE configuration mode
Connections and wiring diagram
plugs:
Actuators including DPS, are adjustetd and equiped with three plugs. You can see the wiring on the actuators imprint or the wiring
diagram.
model S 20/ 35/ 55/ 85
model H/L 140/ 300
plug 1:
power supply (according to label)
plug 2:
driving signal (0 -10 V, 4 - 20 mA orr 0
– 20 mA)
plug 3:
limit switch signal open/close (potential free)
Abb. 4