- 30 -
A c t u a t o r s w i t h B a t t e r y S p r i n g R e t u r n
To prevent an unwanted „Opening“ or „Closing“ by the valve, it is advisable to separate
the actuator from the valve.
Technical data:
Status
Time
Indicator
Actuator without power and working
with the BSR system, max. 3 minutes
200 msec
1000 1000 1000 1000
Actuator without power and working
with the BSR system, max. 3 minutes
200 msec
1000 1000 1000 1000
Battery protection. Danger
The battery needs recharging. BSR disabled.
200 msec
1010 1000 0000 0000
LED Status
Red
Green
Orange
Status-LED
Model
S20
S35
S55
S85
H140/300
L140/300
Capacity
1000 mA
Full charge time 100%
28 Std.
Charging time after drive
8min
8min
10min
20min
30min
50min
Battery consumption/ working operation
6,2W
23W
Working operation without recharge
5
2
1
Configuration security option (NO/NC)
Jumper on position “SELDIR”
with jumper
=
NC (‚closed‘)
without jumper = NO (‚open‘)
Battery charge
40mA/h
Working operation with battery
2,4mA
3,3mA
7,1mA
15,1mA
25,7mA
Weight (BSR Kit)
0,23kg
0,375kg
There is no servicing required! Regular functional checks, must be scheduled, considering to the
secruity requirement. To make a functional test, do it in the following way:
Take away the actuator from power supply and toggle it from “automatic” to “manual. Unloose the
four fixing screws at the flange and detach the the actuator from the valve. Turn the actuator
manually out of position (min. 45°). Afterwards you have to toggle the actuator back to „automatic“
and switch on the power supply for short-time. If the actuator initiate, switch off the power supply
immediatly. Now the actuator have to drive in it defined position (Open or Closed). In the end, you
have to attach the actuator back on the valve.
Functional check