Wiring diagram DPS AC/DC
Error analysis (FAQ)
The actuator positions are not acc. to the input signal
reason: drive over the adjusted angel by hand
help: see chapter “adjust the DPS positioner systems “
The actuator drives in the wrong direction at positioner signal (e.g. 0 V = valve is opened)
reason: valve is wrong mounted or the rotating direction is changed
help: see chapter “adjust the DPS positioner systems “
The motor cams are adjusted by the user but the actuator drives in the same position like before.
reason: after the adjustment of the cams you have to adjust the DPS system too
help: see chapter “adjust the DPS positioner systems “
The angel positions are not according to the signal. The actuator stopps earlier
reason: the motor stop cam is adjusted in the adjustment area of the DPS System
help: see chapter “Adjust working angel” after it chapter “adjust the DPS positioner systems “
The volt free contacts have no function after arrive to the end position
reason: the cam doesn't arrive the position or is adjusted
help: adjust the cam as its shown in the main manual
A c t u a t o r s w i t h D P S P o s i t i o n e r
- 34 -