57
• The fireplace must be disconnected from the gas supply system when components that measure
intake gas pressure are being installed. Once the gas supply is reconnected, check all connections as
well as the gas meter (or tank) connected to the fireplace for tightness. Make sure there are no leaks
(sees section 6.6).
6.5. PROCEDURE FOR CHECKING GAS PRESSURE FROM THE
FIREPLACE VALVE
• Make sure the manual valve is closed.
• Loosen the input “IN” and/or the output “OUT”
pressure verification port(s) by turning counter
clockwise with a 1/8 in. (3 mm) wide screwdriver
(figure 6.5).
• Connect the pressure gauge to the input “IN”
and/or output “OUT” pressure verification port(s)
using a rubber hose with a 5/16 in. (8 mm) inner
diameter.
• Open the manual valve (you will get the intake
pressure).
• Turn on the fireplace to check outlet pressure.
• When you are done reading the pressure gauge,
turn off the fireplace, close the manual valve, disconnect the hose and tighten the screw(s) (clockwise)
with a small flat screwdriver (1/8 in. wide).
• Make sure the output pressure of the automatic valve is comprised between the numbers listed in this
table.
WARNING
Never use an open flame to check for gas leaks.
Figure 6.5
CAUTION
A manual shut-off valve must be installed before
the
SmartCase
®
. It must be easy to access (see figure
6.2).
WARNING
Connection must be performed by a certified
installer.