40
3.2.3.7.
W
ALL OUTLET CONFIGURATION EXAMPLE
ASSEMBLY WITH 1 90° ELBOW
For a horizontal exhaust where Vt is between 6 in.
and 16 in we have Ht
<
4’
Vertical rise
V1 =0.5 feet.
Horizontal run
H1 =4 feet.
Total vertical rise
V
t
= 0.5 feet
Horizontal equivalent of elbows
H
e
= 3 feet (for a 90°elbow)
N= 1 (qty of elbow)
H
C
= (N - 1) x H
e
= 0 x 3 feet. = 0 feet.
Total horizontal run
H
t
= 0 ft. + 4 ft. = 4 ft.
0.5 < vertical rise < 1.33 ft.
0.5
<
0.5pi
<
1.33pi
Because 0.5ft. < V
t
< 1.33 ft. use H
t
< 4 ft.
Total distance H
t
+ V
t
<40 ft.
4 ft. + 0.5 ft. = 4.5 ft.
4.5 ft. < 40 ft.
This assembly is accepted.