Page 5-36
ITW Dynatec
Revised 1/16
V6 DCL Touch Screen Controller for Dynamelt M & D ASUs
Calibrating Screen
Item Description
1
Parameter Selection tabs
The Pressure Zero Calibration tab has been selected.
2
Pressure Zero Calibration
If (optional) pressure sensors are installed on the unit, the pumps can be pressure controlled.
Pressure values will be displayed on the Main Screen. Refer to Pump Control, Pressure
Control. Primary and Secondary Pressure Ports are displayed on the screen. Calibrate each
pump to zero by pressing the appropriate "Cal" button. Note: before calibrating pressure
transducers, all pumps must be in STOP mode and the system must be fully depressurized.
3
Calibrate All
Press the Calibrate All button to calibrate all pumps to zero at one time. Note: before
calibrating pressure transducers, all pumps must be in STOP mode and the system must be
fully depressurized.
4
Press the left-pointing arrow to go to the previous General Settings screen.
5
Press the right-pointing arrow to go to the next General Settings screen.
6
Press the OK button to confirm your entered values and return to the previous screen.
7
Press the ESC button to discard any non-confirmed values and return to the previous screen.
6
7
1
2
4
5
3
Summary of Contents for DYNAMELT D15 Series
Page 3: ......
Page 4: ......
Page 10: ...Page viii Revised 11 14 ITW Dynatec D15 D25 D45 V6 DCL ASU Manual 20 63 ...
Page 22: ...Page 2 8 Description Revised 10 14 ITW Dynatec D15 D25 D45 V6 DCL ASU Manual 20 63 ...
Page 76: ...Page 5 28 LCD Programming Revised 10 14 ITW Dynatec D SERIES V6 DCL ASU Manuals ...
Page 148: ...Page 7 14 Troubleshooting Revised 10 14 ITW Dynatec D SERIES V6 DCL ASU Manuals ...