LCD Programming Page 5-7
Revised 10/14
Selecting Temperature Setpoints
After selecting a temperature zone, press the Enter Knob to highlight the setpoint. Turn the In
‐
put Wheel to your desired setpoint value. To enter the new value, press the Enter Knob. Contin
‐
ue programming by entering a setpoint for each zone.
NOTE for systems with multiple ASU zones (ie. multiple Premelt, Hopper and Filter Block zones):
each of the ASU zone pairs are individually controlled by RTD sensors, but require only one tem
‐
perature setpoint. For example, a system with two Premelt zones, two Hopper zones and two
Filter Block zones only requires that one Premelt setpoint be programmed, one Hopper setpoint
be programmed and one Filter Block setpoint be programmed. NOTE: on the D Series models,
there never more than one Hopper or one Filter Block.
Turning a Temperature Zone ON or OFF
When a temperature zone is not used, it can be de
‐
activated (turned OFF). A zone that is turned
off no longer heats and is not monitored by the controller for over or under temperatures.
Even when a zone is turned off, the controller remembers its temperature setpoint and it will be
restored when the zone is turned back on.
To toggle a temperature zone ON or OFF, press the Enter Knob. Then press F5. You will see the
ON/ OFF switch change position. Press the Enter Knob.
Zone is ON,
Setpoint is highlighted
Zone is OFF,
Setpoint is displayed as “
‐ ‐ ‐
”
Press F5 to turn zone
ON or OFF
ON/ OFF switch
Summary of Contents for DYNAMELT D15 Series
Page 3: ......
Page 4: ......
Page 10: ...Page viii Revised 11 14 ITW Dynatec D15 D25 D45 V6 DCL ASU Manual 20 63 ...
Page 22: ...Page 2 8 Description Revised 10 14 ITW Dynatec D15 D25 D45 V6 DCL ASU Manual 20 63 ...
Page 76: ...Page 5 28 LCD Programming Revised 10 14 ITW Dynatec D SERIES V6 DCL ASU Manuals ...
Page 148: ...Page 7 14 Troubleshooting Revised 10 14 ITW Dynatec D SERIES V6 DCL ASU Manuals ...