Goodrive3000 series medium voltage VFD Goodrive3000 PWM rectifier
-52-
Function
Name
Description
4
Valid value of the input
current
*10, A
5
Input power
*10, kW
6
Input power factor
*100
7
Grid frequency value *10, Hz
8
Active current feedback 100% corresponds to the rated current of the rectifier
9
Reactive current
feedback
100% corresponds to the rated current of the rectifier
10
Fault code
11
AI1
*100, V
12
AI2
*100, V
13
AI3
*100, V
14
Input state
15
Output state
16
Running status word
17
–20
Reserved
P12.13
–P12.23 can be modified in any state.
Function
code
Name
Description
Setting range
Default
P12.24
Temporary variable
1 of PZD sending
0
–65535
0
–65535
0
The function code is used as temporary variable for PZD sending.
P12.24 can be written in any state.
Function
code
Name
Description
Setting range
Default
P12.25
Time of DP
communication
overtime fault
0.0 (invalid), 0.1
–60.0s
0.0
–60.0
0.0s
If the function code is set to 0.0s, the fault is invalid. If it is set to a non-zero value (actual value, unit:
second), if the interval time between two communications exceeds the set time, the system reports E-DP.