10 Ethernet communication
The VFD has been integrated with Ethernet communication function. Ethernet communication can be
implemented by connecting the VFD to the upper computer that hosts the Ethernet upper computer
monitoring software (available at www.invt.com) with a standard Ethernet RJ45 cable.
You can easily set, upload, and download all VFD parameters by using the upper computer. You can also
monitor more than 100 internal information waveforms of theVFD in real time.
10.1 Operating procedure
See the operating manual of INVT Workshop upper computer monitoring system.
The VFD provides the "black box" function. The VFD can save the waveform information generated
within 0.2s before the most recent fault that causes its stop. You can obtain the waveform information
from the upper computer and analyze fault causes.
10.2 Related function codes
Rectifier related function codes
Function
code
Name
Description
Setting range
Default
P13.00
Ethernet
communication rate
0: Self adaptive
1: 100M full duplex
2: 100M half duplex
3: 10M full duplex
4: 10M half duplex
0
–4
0
P13.01
IP address 1
0
–255
0
–255
192
P13.02
IP address 2
0
–255
0
–255
168
P13.03
IP address 3
0
–255
0
–255
0
P13.04
IP address 4
0
–255
0
–255
1
P13.05
Subnet mask 1
0
–255
0
–255
255
P13.06
Subnet mask 2
0
–255
0
–255
255
P13.07
Subnet mask 3
0
–255
0
–255
255
P13.08
Subnet mask 4
0
–255
0
–255
0
P13.09
Gateway 1
0
–255
0
–255
192
P13.10
Gateway 2
0
–255
0
–255
168
P13.11
Gateway 3
0
–255
0
–255
1
P13.12
Gateway 4
0
–255
0
–255
1