Goodrive3000 series medium voltage VFD Goodrive3000 PWM rectifier
-25-
Function
code
Name
Description
Setting range
Default
P00.04
DC bus voltage
setting
0: Automatic
1: Keypad setting
2: Reserved
0
–2
1
P00.05
Setting value of DC
bus voltage
300.0
–4000.0V
300.0
–4000.0
Depends
on model
When P00.04=1, P00.05 DC bus voltage is set by keypad.
The relation between the voltage and DC bus voltage:
VFD
Default value of DC bus voltage
(P00.05)
Overvoltage point
1140V
1850V
2300V
Function
code
Name
Description
Setting range
Default
P00.08
Resonance
suppression factor
0
–10
0
–10
0
Function
code
Name
Description
Setting range
Default
P00.09
Overmodulation
selection
0: Invalid
1: Valid
0
–1
1
Function
code
Name
Description
Setting range
Default
P00.10
Running mode of
cooling fan
0: Normal running mode
1: Keep running after power on
0
–1
0
Set the running mode of cooling fan.
0: Normal running mode: after the rectifier receives the running command or the detection temperature of
the rectifier is higher than 45°C or the current of the rectifier is higher than 50% of the rated current, the
cooling fan will run.
1: Keep running after power on (applicable to high temperature and humidity situations)
Function
code
Name
Description
Setting range
Default
P00.14
Carrier frequency 2.0
–8.0kHz
2.0
–8.0
4.0
P00.15
Function parameter
restore
0: No operation
1: Restore the default value
0
–3