Goodrive3000 series medium voltage VFD Goodrive3000 PWM rectifier
-33-
Setting value
Function
Description
misaction.
1
Run
Control the operation through external terminals.
2
Fault reset
External fault reset, same as the function of STOP/RST.
Remote fault reset is available by the function.
3
External fault
PWM rectifier reports fault and stops when external fault
signal is sent to the rectifier. The main contactor does
not switch off and the diode rectifier works normally.
4
Reserved
5
Run enabling
PWM rectifier works after the enabling terminal is valid.
6
–12
Reserved
13
Total electricity
consumption cleared
Total electricity consumption is cleared if the command
is valid (P07.17 and P07.18).
14
Accumulative power
maintain
The current operation does not affect the accumulative
power if the command is valid.
15
Reserved
Function
code
Name
Description
Setting range
Default
P05.12
Delay time of S1
switching-on
The function codes are used to set
the delay time when electric level
changes.
0.000
–60.000s
0.000s
P05.13
Delay time of S1
switching-off
0.000s
P05.14
Delay time of S2
switching-on
0.000s
P05.15
Delay time of S2
switching-off
0.000s
P05.16
Delay time of S3
switching-on
0.000s
P05.17
Delay time of S3
switching-off
0.000s
P05.18
Delay time of S4
switching-on
0.000s
P05.19
Delay time of S4
switching-off
0.000s