Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-122-
Function
code
Name
Description
Setting range
Default
P06.19
AO3 output
2: Ramp reference frequency
3: Running rotating speed
4: Output current (Relative to VFD)
5: Output current (Relative to motor)
6: Output voltage
7: Output power
8: Set torque value
9: Output torque
10: AI1 input value
11: AI2 input value
12: AI3 input value
13: HDI pulse frequency input value
14: MODBUS communication set
value 1
15: MODBUS communication set
value 2
16: PROFIBUS/CANopen
communication set value 1
17: PROFIBUS/CANopen
communication set value 2
18: Ethernet communication set
value 1
19: Ethernet communication set
value 2
20: PID reference
21: PID feedback
22: Torque current (Relative to motor
rated current)
23: Ramp reference frequency (with
sign)
24
–30: Reserved
0
–30
0
P06.20
HDO pulse output
0
–30
0
Instructions to output functions:
Set value
Function
Instruction
0
Running frequency
0
– Max. output frequency
1
Set frequency
0
– Max. output frequency