Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-210-
Function
code
Name
Description
Setting range
Default Modify
12: AI3 input value
13: HDI pulse frequency input value
14: MODBUS communication set value
1
15: MODBUS communication set value
2
16: PROFIBUS/CANopen
communication set value 1
17: PROFIBUS/CANopen
communication set value 2
18: Ethernet communication set value 1
19: Ethernet communication set value 2
20: PID reference
21: PID feedback
22: Torque current (Relative to motor
rated current)
23: Ramp reference frequency (with
sign)
24
–
30: Reserved
P06.21
Lower limit of
AO1 output
-100.0%
–P06.23
-100.0
–P06.23
0.0%
○
P06.22
Corresponding
AO1 output to
lower limit
-10.00V
–10.00V
-10.00
–10.00
0.00V
○
P06.23
Upper limit of
AO1 output
P06.21
–100.0%
P06.21
–100.0
100.0%
○
P06.24
Corresponding
AO1 output to
upper limit
-10.00V
–10.00V
-10.00
–10.00
10.00V
○
P06.25
AO1 output filter
time
0.000s
–10.000s
0.000
–10.000
0.000s
○
P06.26
Lower limit of
AO2 output
-100.0%
–P06.28
-100.0
–P06.28
0.0%
○
P06.27
Corresponding
AO2 output to
lower limit
-10.00V
–10.00V
-10.00
–10.00
0.00V
○