![INVT GD3000-01-055G-12 Operation Manual Download Page 166](http://html1.mh-extra.com/html/invt/gd3000-01-055g-12/gd3000-01-055g-12_operation-manual_2085697166.webp)
Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-161-
Function
code
Name
Description
Setting range
Default
iron core of AM 2
P12.26
Motor 2 overload
protection
0: No protection
1: Common motor (with low speed
compensation)
2: Frequency conversion motor
(without low speed compensation)
0
–2
2
P12.27
Motor 2 overload
protection coefficient
20.0%
–120.0%
20.0
–120.0
100.0%
P12.28
Motor 2 power
correction coefficient
0.00
–3.00
0.00
–3.00
1.00
P12.31
Motor 2 parameter
display
0: Display according to motor type
1: Display all parameters
0
–1
0
For the parameter settings of synchronous motor 2, refer to the settings of synchronous motor 1 in P02