Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-102-
Output voltage
Output
frequency(Hz)
V1
V2
V3
f1
f2
f3
100.0%
b
f
b
V
Function
code
Name
Description
Setting range
Default
P04.09
Motor 1 V/F slip
compensation gain
0.0
–200.0%
0.0
–200.0
100.0%
This function code is used to compensate the change of the rotating speed caused by the change of load
at V/F control to improve mechanical rigidity of the motor. The rated slip frequency of the motor should be
calculated as follows:
△
f=f
b
-n*p/60
Of which, f
b
is motor rated frequency, corresponding to the function code P02.02; n is motor rated speed,
corresponding to the function code P02.03; p is motor pole pair, 100.0% corresponding to the rated slip
frequency
△
f.
Function
code
Name
Description
Setting range
Default
P04.10
Motor 1 low
frequency oscillation
control factor
0
–100
0
–100
10
P04.11
Motor 1 high
frequency oscillation
control factor
0
–100
0
–100
10
P04.12
Motor 1 oscillation
control threshold
0.00Hz
–P00.03 (Max. frequency)
0.00
–P00.03
30.00Hz
Under V/F control mode, especially the motor with big power, current oscillation may occur to some
frequency, causing unstable running of the motor or even VFD overcurrent. Eliminate the results by
adjusting the parameters properly.