Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-193-
Function
code
Name
Description
Setting range
Default Modify
P01.11
DC braking
current
0.0
–100.0% (Motor rated current)
0.0
–100.0
0.0%
○
P01.12
DC braking time 0.0
–50.0s
0.0
–50.0
0.0s
○
P01.13
Dead time of
FWD/REV
rotation
0.0
–3600.0s
0.0
–3600.0
0.0s
○
P01.14
Shifting between
FWD/REV
rotation
0: Switch after 0 frequency
1: Switch after starting frequency
2: Switch after delay at stop speed
(Reserved)
0
–2
0
◎
P01.15
Stop speed
0.00
–100.00Hz
0.00
–100.00
0.50 Hz
◎
P01.16
Detection of stop
speed
0: Speed set value (delay without
stopping)
1: Speed detecting value (only valid
under vector control)
0
–1
1
◎
P01.17
Detection time of
feedback speed
0.0
–100.0s (only valid for P01.16=1)
0.00
–100.00
0.50s
◎
P01.18
Terminal running
protection when
power on
0: Terminal running command is invalid
when power on
1: Terminal running command is valid
when power on
0
–1
0
○
P01.19
The running
frequency is lower
than the lower limit
one (valid if the
lower limit
frequency is
above 0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
0
–2
0
◎
P01.20
Hibernation
restore delay
time
0.0
–
3600.0s (valid when P01.19=2)
0.0
–3600.0
0.0s
○
P01.21
Restart after
power off
0: Disabled
1: Enabled
0
–1
0
○
P01.22
Waiting time of
restart after
power off
0.0
–
3600.0s
0.0
–3600.0
1.0s
○