Goodrive3000 series medium voltage VFD Goodrive3000 inverter
-235-
Function
code
Name
Description
Setting range
Default Modify
P15.19
Sent PZD8
7: Output power actual value
8: Rotating speed during running
9: Running linear speed
10: Ramp reference frequency
11: Fault code
12: AI1 value
13: AI2 value
14: AI3 value
15: PULSE frequency
16: Input state of terminals
17: Output state of terminals
18: PID reference
19: PID feedback
20: Motor rated torque
0
–20
0
○
P15.20
Sent PZD9
0
–20
0
○
P15.21
Sent PZD10
0
–20
0
○
P15.22
Sent PZD11
0
–20
0
○
P15.23
Sent PZD12
0
–20
0
○
P15.24
Temporary
variable 1 for
PZD sending
0
–65535
0
–65535
0
○
P15.25
DP
communication
timeout fault
duration
0.0: Invalid
0.1
–60.0s
0.0
–60.0
0.0s
○
P15.26
CANopen
communication
timeout fault
duration
0.0 (invalid)
0.1
–60.0s
0.0
–60.0
0.0s
○
P15.27
CANopen baud
rate
0: 1000k
1: 800k
2: 500k
3: 250k
4: 125k
5: 100k
6: 50k
7: 20k
0
–7
0
◎
P15.28
CAN
communication
address
0
–127
0 is broadcast communication address
0
–127
1
◎