Goodrive20-EU series VFD
Function parameters
87
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
1: main reference A frequency source buffering
acceleration/deceleration is valid and the
acceleration/deceleration is determined by
P08.04.
P09.15
PID command
acceleration/
deceleration
time
0.0
– 1000.0s
0.0s
○
P09.16
PID output filter
time
0.000
– 10.000s
0.000s
○
P09.17
Low frequency
proportional
gain (Kp)
0.00
– 100.00
1.00
○
P09.18
Low frequency
integral time
(Ti)
0.00
– 10.00s
0.10s
○
P09.19
Low frequency
differential time
(Td)
0.00
– 10.00s
0.00s
○
P09.20
Low point
frequency of
PID parameter
switching
0.00Hz
When the ramp frequency is no greater than
P09.20, current PID parameters are P09.17
P09.19. When the ramp frequency is no less
than P09.21, current PID parameters are P09.04
– P09.06. The medium frequency range is the
linear interpolation values between the two PID
parameter groups.
5.00Hz
○
P09.21
High point
frequency of
PID parameter
switching
10.00Hz
○
P10 Group Simple PLC and multi-step speed control
P10.00
Simple PLC
mode
0: Stop after running once. The VFD has to be
commanded again after finishing a cycle.
1: Run at the final value after running once. After
finish a signal, the VFD will keep the running
frequency and direction of the last run.
0
○