Goodrive20-EU series VFD
Function parameters
61
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
Sln
FWD
REV
Direction
ON
OFF→ON
ON
Forward
OFF
Reverse
ON
ON
OFF→ON
Forward
OFF
Reverse
ON→
OFF
Decelerate
to stop
Note
: For the 2-wire running mode, when
FWD/REV terminal is valid, the VFD stop
because of the stopping command from other
sources, even the control terminal FWD/REV
keeps valid; the VFD won't work when the
stopping command is canceled. Only when
FWD/REV is re-launched, the VFD can start
again. For example, the valid STOP/RST stop
when PLC signal cycles stop, fixed-length stop
and terminal control (see P07.04).
P05.14
S1 terminal
switching on
delay time
The function code defines the corresponding
delay time of electrical level of the programmable
terminals from switching on to switching off.
Si electrical level
Si valid
invalid
invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.000
– 50.000s
0.000s
○
P05.15
S1 terminal
switching off
delay time
0.000s
○
P05.16
S2 terminal
switching on
delay time
0.000s
○
P05.17
S2 terminal
switching off
delay time
0.000s
○
COM
SB2
SB1
FWD
REV
SIn
SB3
Summary of Contents for GD20-004G-2-EU
Page 1: ......
Page 168: ...6 6 0 0 1 0 0 4 8 4 201912 V1 6...