Goodrive20-EU series VFD
Communication protocol
131
Function instruction
Address
definition
Data meaning instruction
R/W
attribute
Setting frequency
3001H
Range: 0.00Hz
R
Bus voltage
3002H
Range: 0
– 2000V
R
Output voltage
3003H
Range: 0
– 1200V
R
Output current
3004H
Range: 0.0
– 3000.0A
R
Operation speed
3005H
Range: 0
– 65535RPM
R
Output power
3006H
Range: -300.0
– 300.0%
R
Output torque
3007H
Range: -250.0
– 250.0%
R
Close loop setting
3008H
Range: -100.0%
– 100.0%
R
Close loop feedback
3009H
Range: -100.0%
– 100.0%
R
PID setting
3008H
-100.0
– 100.0% (unit: 0.1%)
R
PID feedback
3009H
-100.0
– 100.0% (unit: 0.1%)
R
Input IO
300AH
000
– 1FF
Input IO
300BH
000
– 1FF
AI 1
300CH
Range: 0.00
– 10.00V
R
AI 2
300DH
Range: 0.00
– 10.00V
R
AI 3
300EH
Range: 0.00
– 10.00V
R
AI 4
300FH
Range: -10.00
– 10.00V
R
Read high speed pulse
1 input
3010H
Range: 0.00
– 50.00kHz
R
Read high speed pulse
2 input
3011H
Reserved
R
Read current step
number of multi-step
speed
3012H
Range: 0
– 15
R
External length
3013H
Range: 0
– 65535
R
External counting
value
3014H
Range: 0
– 65535
R
Torque setting
3015H
-300.0
– 300.0% (Unit: 0.1% )
R
VFD code
3016H
R
Fault code
5000H
R
R/W characteristics means the function is with read and write characteristics. For example,
"communication control command" is writing chrematistics and control the VFD with writing
command (06H). R characteristic can only read other than write and W characteristic can only
write other than read.
Note:
When operating on the VFD with the table above, it is necessary to enable some
parameters. For example, the operation of running and stopping, it is necessary to set P00.01
Summary of Contents for GD20-004G-2-EU