Goodrive20-EU series VFD
Product overview
6
3. Perform commissioning on the machine in jogging mode and check whether the
rotating direction of the motor meets the requirement. If no, exchange the wires of any
two phases of the motor to change the running direction of the motor.
4. Set all control parameters and then run the machine.
2.2 Data related to safety standards
IEC/EN 61058 (type A system)
ISO 13849**
SIL
PFH
HFT SFF
λdu
λdd
PTI* PL CCF MTTFd DC Category
2 8.73*10
-10
1 71.23% 1.79*10
-9
0
1 year d
57
343.76
year
60%
3
3 8.53*10
-10
1 99.38% 0.64*10
-10
3.3*10
-9
3
months
e
57
207.04
year
98.09%
3
* PTI: proof test interval
** According to the categorization defined in EN ISO 13849-1:2015.
2.3 Decommissioning
Before decommissioning any safety system from active service:
•
Evaluate the impact of decommissioning on adjacent operating units and facilities or
other field services.
•
Conduct a proper review and obtain required authorization.
•
Ensure that the safety functions remain appropriate during decommissioning activities.
•
Implement appropriate change management procedures for all decommissioning
activities.
2.4 Product specifications
Function
Specification
Power input
Input voltage (V)
AC 1PH 200V
–240V, rated voltage: 230V
AC 3PH 200V
–240V, rated voltage: 230V
AC 3PH 380V
–480V, rated voltage: 400V
Allowable voltage
fluctuation
-15%
– +10%
Summary of Contents for GD20-004G-2-EU