Goodrive20-EU series VFD
Communication protocol
125
storage is 0004, read two words continuously, the structure of this frame is listed as below:
ASCII master command message (the
command sent from the master to the VFD
ASCII slave response message (the
message sent from the VFD to the master)
START
':'
START
':'
ADDR
'0'
ADDR
'0'
'1'
'1'
CMD
'0'
CMD
'0'
'3'
'3'
High bit of starting address
'0'
Byte number
'0'
'0'
'4'
Low bit of starting address
'0'
High bit of data address 0004H
'1'
'4'
'3'
High bit of data number
'0'
Low bit of data address 0004H
'8'
'0'
'8'
Low bit of data number
'0'
High bit of data address 0005H
'0'
'2'
'0'
LRC CHK Hi
'F'
Low bit of data address 0005H
'0'
LRC CHK Lo
'6'
'0'
END Hi
CR
LRC CHK Hi
'5'
END Lo
LF
LRC CHK Lo
'D'
END Hi
CR
END Lo
LF
7.3.2.2 Command code: 06H (0000 0110), writing one word
For instance: Write 5000 (1388H) to the 0004H address of the VFD whose slave address is
02H, then the structure of this frame is listed as below:
ASCII master command message (the
command sent by the master to VFD)
ASCII slave response message (the
message sent by the VFD to master)
START
':'
START
':'
ADDR
'0'
ADDR
'0'
'2'
'2'
CMD
'0'
CMD
'0'
'6'
'6'
High bit of write data
'0'
High bit of write data
'0'
'0'
'0'
Low bit of write data
'0'
Low bit of write data
'0'
'4'
'4'
High bit of data
'1'
High bit of data
'1'
Summary of Contents for GD20-004G-2-EU
Page 1: ......
Page 168: ...6 6 0 0 1 0 0 4 8 4 201912 V1 6...