Goodrive20-EU series VFD
Technical data
142
VFD of category C4: VFD of rated voltage more than 1000 V or the nominal current is above or
equal to 400A and used in the complicated system in second environment
A.3.1 Category C2
The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the options and installed as specified in the
EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
In a domestic environment, this product may cause radio inference, in
which case supplementary mitigation measures may be required.
A.3.2 Category C3
The immunity performance of the drive complies with the demands of IEC/EN 61800-3,
second environment.
The emission limits are complied with the following provisions:
1. The optional EMC filter is selected according to the options and installed as specified in the
EMC filter manual.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
A drive of category C3 is not intended to be used on a low-voltage public
network which supplies domestic premises. Radio frequency
interference is expected if the drive is used on such a network.
Summary of Contents for GD20-004G-2-EU
Page 1: ......
Page 168: ...6 6 0 0 1 0 0 4 8 4 201912 V1 6...