Goodrive20-EU series VFD
Function parameters
42
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
immediately. And the load coasts to stop at the
mechanical inertia.
P01.09
Starting
frequency of
DC braking
while stop
Starting frequency of DC braking: start the DC
braking when running frequency reaches starting
frequency determined by P01.09.
Waiting time before DC braking: VFDs blocks the
output before starting the DC braking. After this
waiting time, the DC braking will be started so as
to prevent over-current fault caused by DC
braking at high speed.
DC braking current: the value of P01.11 is the
percentage of rated current of VFD. The bigger
the DC braking current is, the greater the braking
torque is.
DC braking time: the retention time of DC
braking. If the time is 0, the DC braking is invalid,
and the VFD will coast to stop.
P01.04
ACC
P1314
.
P0123
.
Constant
speed
In running
DEC
P0110
.
P1315
.
P01.12
P01.09
t
Setting range of P01.09: 0.00Hz
(the max. frequency)
Setting range of P01.10: 0.00
– 50.00s
Setting range of P01.11: 0.0
– 100.0%
Setting range of P01.12: 0.00
– 50.00s
0.00Hz
○
P01.10
Stop brake
waiting time
0.00s
○
P01.11
Stop DC
braking current
0.0%
○
P01.12
Stop DC
braking time
0.00s
○
P01.13
Deadzone time
of FWR/REV
rotation
During the procedure of switching FWD/REV
rotation, set the threshold by P01.14, which is as
the table below.
0.0s
○