10
Decommissioning
and disassembly
10.2
Disassembly
112
INTILION GmbH
10.2.2.6 Disassembling the cables for the lithium-ion batteries
DANGER
There is a risk of electric shock when touching parts that are under
voltage.
The individual lithium-ion batteries cannot be de-energised. There is
always dangerous electrical voltage at the power connections on the
lithium-ion batteries.
–
Proceed step by step when disassembling.
–
When removing the safety caps from a lithium-ion battery, make sure that
the safety caps are in place on the respective poles on all other lithium-
ion batteries.
Illustration 65: Lithium-ion batteries - removing the safety caps
•
Push the safety caps on the poles (1) upwards (2), and remove in the direction of the
arrow (3).
•
Disassemble the cables.
•
Put the safety caps back onto the poles in reverse order.
•
Disassemble the cables in the same way for all other lithium-ion batteries.