3
Description
of the battery storage system
3.2
Overview
INTILION scalebloc 0.5C
39
3.2.4.3
Alarm
Illustration 8: Alarm
The visual and acoustic alarm signalises the system’s error states
(e.g. doors remaining open for more than half an hour or a triggered smoke detector).
The signal colour is red.
The acoustic signal takes the form of a constant warning tone when the smoke detector is
triggered. By contrast, if the doors are open, the acoustic signal takes the form of a
repeated brief tone.
3.2.4.4
Emergency stop contacts
There are connection terminals on the ControlShield for the integration of an emergency
stop switch or an emergency stop/safety circuit.
If this circuit is interrupted, the battery storage system will be disconnected from the
network by an integrated circuit breaker. If this disconnection is not desired, the
corresponding terminals will need to be bridged. These bridges are factory-fitted as
standard.
Illustration 9: Emergency stop contacts