5
Installation
5.8
Power cabling
of the lithium-ion batteries
62
INTILION GmbH
•
Put the safety caps back on.
•
Use the 340-mm-long cell connector to connect connection B- on the battery
management system (BMS) to the negative pole (-) of battery module 1 (Bat 1).
•
Put the safety caps back on.
The subsequent steps involve the laying of the 560-mm-long cell connectors as follows:
Illustration 24: Laying the cell connectors
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 1 to the negative pole (-) of battery module 2.
•
Put the safety caps back on.
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 2 to the negative pole (-) of battery module 3.
•
Put the safety caps back on.
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 4 to the negative pole (-) of battery module 5.
•
Put the safety caps back on.
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 5 to the negative pole (-) of battery module 6.
•
Put the safety caps back on.
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 6 to the negative pole (-) of battery module 7.
•
Put the safety caps back on.
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 7 to the negative pole (-) of battery module 8.
•
Put the safety caps back on.
•
Use the 560-mm-long cell connector to connect the positive pole (+) of battery
module 8 to the negative pole (-) of battery module 9.
•
Put the safety caps back on.
Summary of Contents for scalebloc 0.5C
Page 33: ...2 Safety 2 10 Obligations of the system manager INTILION scalebloc 0 5C 31 ...
Page 34: ......
Page 46: ...4 Transport and storage 3 3 Technical specifications 44 INTILION GmbH ...
Page 77: ...5 Installation 5 12 Establishing the mains connection INTILION scalebloc 0 5C 75 ...
Page 78: ......
Page 98: ...6 Commissioning 6 8 Contacting the Hoppecke Service team 96 INTILION GmbH ...
Page 100: ......
Page 102: ...8 Fault 100 INTILION GmbH ...