Control_ Vanes U-D / 5 pos
1 byte
DPT_Enumerated
5.010
W T 1 - Pos1; 2 - Pos2; 3 - Pos3;
4 - Pos4; 5 - Pos5
19
Control_ Vanes U-D Man/Auto
1 bit
DPT_Bool
1.002
W T
0
–
Manual; 1 - Auto
20
Control_ Vanes U-D Pos1
1 bit
DPT_Bool
1.002
W T 1
–
Set Position 1
21
Control_ Vanes U-D Pos2
1 bit
DPT_Bool
1.002
W T 1
–
Set Position 2
22
Control_ Vanes U-D Pos3
1 bit
DPT_Bool
1.002
W T
1
–
Set Position 3
23
Control_ Vanes U-D Pos4
1 bit
DPT_Bool
1.002
W T 1
–
Set Position 4
24
Control_ Vanes U-D Pos5
1 bit
DPT_Bool
1.002
W T 1
–
Set Position 5
25
Control_ Vanes U-D Swing
1 bit
DPT_Bool
1.002
W T 0
–
Off; 1
–
Swing
26
Control_ Vanes U-D +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Vanes U-D +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
Temperature
27
Control_ Setpoint Temperature
2 byte
DPT_Value_Temp
9.001
W T
(ºC)
28
Control_ Setpoint Temp +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Setpoint Temp +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
29
Control_ Ambient Temperature
2 byte
DPT_Value_Temp
9.001
W T
(ºC)
Timeout
30
Control_ Window Contact Status
1 bit
DPT_OpenClose
1.009
W T 0 - Open; 1 - Closed
Control_ Switch Off Timeout
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
31
Control_ Occupancy
1 bit
DPT_Occupancy
1.018
W T
0 - Not Occupied; 1 - Occupied
32
Control_ Sleep Timeout
1 bit
DPT_Start
1.010
W T 0 - Stop; 1 - Start
Locking
33
Control_ Lock Remote Control
1 bit
DPT_Bool
1.002
W T 0 - Unlocked; 1 - Locked