When a
“0”
value is sent to the
Control_
communication object, EconoMode
will be disabled, and the
Status_
object will return this value.
Important:
This mode will ONLY work if the indoor unit is both turned on and
in a Heat, Cool, Auto-Heat or Auto-Cool Mode.
➢
Action time for this mode (minutes):
Duration of EconoMode, in minutes, once started.
➢
Setpoint delta increase (HEAT) or decrease (COOL)
–
in Celsius:
Number of degrees Celsius that will increase in Heat Mode, or decrease in Cool Mode,
while in EconoMode.
➢
Fan Speed for this mode:
Fan Speed that will be set in the unit while in EconoMode.
4.3.3 Enable use of ADDITIONAL HEATING mode
This parameter shows/hides the
Control_ Start Additional Heat Mode
and
Status_ Additional
Heat Mode
communication objects. The Additional Heating Mode lets change the Setpoint
Temperature and the Fan Speed within a given period of time.
o
If set to
“no”
the objects will not be shown.
o
If set to
“yes”
the Control_ Start Additional Heat Mode and Status_ Additional Heat
Mode objects and new parameters will appear.
•
When a
“1”
value is sent to the
Control_
communication object, Additional
Heating Mode will be enabled, and the
Status_
object will return this value.
•
When a
“0”
value is sent to the
Control_
communication object, Additional
Heating Mode will be disabled, and the
Status_
object will return this value.
Important:
This mode will ALWAYS turn on the indoor unit in Heat mode.
➢
Action time for this mode (minutes):
Duration of Additional Heating Mode, in minutes, once started.
➢
Setpoint temp for this mode (ºC):
Setpoint temperature that will be applied while in Additional Heating Mode.